background image

2 Safety

The following symbols are used in this document:

WARNING

Indicates a potentially hazardous situation which could
result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation which could
result in minor or moderate injury. It may also be used
to alert against unsafe practices.

NOTICE

Indicates important information, including situations that
may result in damage to equipment or property.

2.1  Qualified Personnel

Correct and reliable transport, storage, installation,
operation and maintenance are required for the trouble-
free and safe operation of the frequency converter. Only
qualified personnel is allowed to install or operate this
equipment.

Qualified personnel is defined as trained staff, who are
authorised to install, commission, and maintain equipment,
systems and circuits in accordance with pertinent laws and
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in this
document.

2.2  Safety Precautions

WARNING

HIGH VOLTAGE

Frequency converters contain high voltage when
connected to AC mains input power. Failure to perform
installation, start up, and maintenance by qualified
personnel could result in death or serious injury.

Only qualified personnel are permitted to
perform installation, start up, and maintenance.

WARNING

UNINTENDED START

When the frequency converter is connected to AC mains,
the motor may start at any time, causing risk of death,
serious injury, equipment, or property damage. The
motor can start by means of an external switch, a serial
bus command, an input reference signal from the LCP or
LOP, or after a cleared fault condition.

Disconnect the frequency converter from mains
whenever personal safety considerations make
it necessary to avoid unintended motor start.

Press [Off/Reset] on the LCP, before
programming parameters.

The frequency converter, motor, and any driven
equipment must be in operational readiness
when the frequency converter is connected to
AC mains.

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work, could result in death or serious
injury.

1.

Stop motor.

2.

Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.

3.

Wait for the capacitors to discharge fully, before
performing any service or repair work. The
duration of waiting time is specified in

Table 2.1

.

Voltage

[V]

Power Range

1)

[kW]

Minimum waiting

time

(min)

3x400

0.55–7.5

4

High voltage can be present even when the warning LED

indicator lights are off.

Table 2.1 Discharge Time

1) Power ratings relate to NO, see VLT

®

 DriveMotor FCP 106 and FCM

106 Operating Instructions.

Safety

VLT

®

 DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions

6

MG03O102 - Danfoss A/S 

©

 12/2013. All rights reserved.

2

2

Summary of Contents for VLT DriveMotor FCP 106

Page 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT DriveMotor FCP 106 and FCM 106 BACnet www danfoss com drives...

Page 2: ......

Page 3: ...3 2 1 EMC Precautions 11 3 2 2 Screen 11 3 2 3 Single Ground Screen 11 4 System Configuration 12 4 1 Configuring BACnet 12 4 2 BACnet Set up Example 13 5 BACnet Objects 14 5 1 Network Frequency Conve...

Page 4: ...7 1 3 Warning Words 27 Index 28 Contents VLT DriveMotor FCP 106 FCM 106 BACnet Operating Instructions 2 MG03O102 Danfoss A S 12 2013 All rights reserved...

Page 5: ...rter from a Windows based PC environment Danfoss VLT Energy Box software for energy calculation in HVAC applications Technical literature and approvals are available online at www danfoss com Business...

Page 6: ...of the device to communicate Function Groups specify a combination of Objects and Services necessary to carry out certain building automation functions They are specified independently of Conformance...

Page 7: ...urpose In no event shall Danfoss be liable for direct indirect special incidental or consequential damages arising out of the use or the inability to use information contained in this manual even if a...

Page 8: ...tor may start at any time causing risk of death serious injury equipment or property damage The motor can start by means of an external switch a serial bus command an input reference signal from the L...

Page 9: ...e 2 separate ground wires both complying with the dimensioning rules NOTICE HIGH ALTITUDES For installation at altitudes above 2000 m contact Danfoss regarding PELV CAUTION SHOCK HAZARD The frequency...

Page 10: ...75 C rated copper wire See VLT DriveMotor FCP 106 and FCM 106 Operating Instructions for recommended wire sizes and types 3 1 2 Special Conditions Electrical ratings The frequency converter rating sh...

Page 11: ...s it connects The number of frequency converters is based on a single master system If there are 2 or more devices e g PC tools Routers reduce the number of frequency converters correspondingly Maximu...

Page 12: ...e control card DIP switch to ON to terminate the RS 485 bus and activate RS 485 For position of DIP switch see Illustration 3 3 The factory setting for the DIP switch is OFF 195NA488 11 1 2 3 1 DIP sw...

Page 13: ...g from one building to another and the problem with difference in ground potential can be ignored 3 2 4 Multiple Ground Screens When the distance between the individual frequency converter is limited...

Page 14: ...rk See also chapter 6 1 Parameter List Parameter Default Value Setting for BACnet 8 50 Coasting Select Logic or Set according to the wiring of the application 8 52 DC Brake Select Logic or Logic or 8...

Page 15: ...rameters Parameter Value 8 30 Protocol 5 BACnet 8 31 Address 20 8 32 Baud Rate 4 38 400 Baud 8 50 Coasting Select 1 Bus 8 70 BACnet Device Instance 1025 8 72 MS TP Max Masters 35 Table 4 5 BACnet Set...

Page 16: ...rminal 42 Output Bus Control 696 N2 x x x AO 2 Terminal 45 Output Bus Control 676 N2 x x x Table 5 2 Analog Outputs ID Object_Name Present_Value Default name Writeable EEPROM Parameter Unit Writeable...

Page 17: ...lues 1 Either AV 1 or AV 2 controls the frequency converter reference Only one of them can control the frequency converter at a time and BV 2 decides which one 2 This value is not directly available i...

Page 18: ...4 95 Load on the Motor is less than programmed limit of system An Example is a broken belt or coupling Configuration Error 15 40 41 Errors exist in the programmed or operational configuration of the i...

Page 19: ...Reserved for VFD profile BV 8 BV 9 BV 10 BV 11 BV 12 BV 13 BV 14 BV 15 BV 16 BV 17 BV 18 BV 19 BV 20 BV 21 Warning x x STW 7 BV 22 Trip x x STW 3 BV 23 Triplock STW 6 BV 24 Coasting CTW 3 x x x BV 25...

Page 20: ...e Select NOTICE 8 01 Control Site overrules the settings in 8 50 Coasting Select to 8 56 Preset Reference Select and Terminal 37 Safe Stop overrules any parameter Each of the digital input signals can...

Page 21: ...Supported x Object List x Max APDU Length x Segmentation Support x Local Time x Local Date x APDU Timeout x Number APDU Retries x Max Master x Max Info Frames x Device Address Binding x Database Revi...

Page 22: ...ct 3 Logic OR All set ups TRUE Uint8 8 53 Start Select 3 Logic OR All set ups TRUE Uint8 8 54 Reversing Select 0 Digital input All set ups TRUE Uint8 8 55 Set up Select 3 Logic OR All set ups TRUE Uin...

Page 23: ...ff 6 2 2 8 3 FC Port Settings 8 30 Protocol Option Function Select the protocol for the integrated RS 485 port 8 30 Protocol Option Function 0 FC Communication according to the FC Protocol 2 Modbus RT...

Page 24: ...erial communi cation port AND additionally via one of the digital inputs 3 Logic OR Activates Quick Stop via the serial communi cation port OR via one of the digital inputs 8 52 DC Brake Select Option...

Page 25: ...selection via the serial communication port 2 Logic AND Activates Preset Reference selection via the serial communication port AND additionally via one of the digital inputs 8 56 Preset Reference Sel...

Page 26: ...Function 0 0 65536 This parameter shows the number of messages sent from the follower 8 85 Slave Timeout Errors Range Function 0 0 65536 This parameter shows the number of follower timeout errors 8 88...

Page 27: ...to the VLT DriveMotor FCP 106 and FCM 106 Programming Guide Warnings All warnings within the frequency converter are represented by a single bit within a warning word A warning word is always an acti...

Page 28: ...AT Earth fault 20000000 Drive initialised 80000000 Table 7 1 16 90 Alarm Word Bit Hex Alarm Word 2 16 91 Alarm Word 2 00000001 00000002 Gate drive voltage fault 00000004 Reserved 00000008 Reserved 000...

Page 29: ...Not used 80000000 Not used Table 7 3 16 92 Warning Word Bit Hex Warning Word 2 16 93 Warning Word 2 00000001 00000002 00000004 00000008 Reserved 00000010 Reserved 00000020 00000040 Dry Pump 00000080...

Page 30: ...ghts 5 D DC current 8 DeviceNet 3 Digital bus settings 12 Discharge time 6 E Electrical ratings 8 EMC Precautions 11 F FC feedback to network 0 Port Diagnostics 23 port settings 12 Port Settings 21 Fu...

Page 31: ...reen 11 T Technical Overview 4 Timeout function 21 U Unintended start 6 W Warning Words 27 Windmilling 7 Wire sizes 8 Index VLT DriveMotor FCP 106 FCM 106 BACnet Operating Instructions MG03O102 Danfos...

Page 32: ...ithout notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in...

Reviews: