ID
Object_Name
Present_Value
Default
name
Writeable
EEPROM
Parameter
Unit
Writeable
Cmd.able
Timeout
AV:22
Running
Hours
1501
Hours
AV:23
kWh Counter
1502
kWh
AV:24
Motor
Voltage
1612
V
AV:25
Frequency
1613
Hz
AV:27
DC Link
Voltage
1630
V
AV:28
Heatsink
Temp.
1634
º
C
AV:29
Inverter
Thermal
1635
%
AV:31
Bus Feedback
1
894
N
2
x
AV:32
Reserved for P, I
AV:33
AV:37
Reserved for P, I
AV:38
AV:39
AV:42
Reserved for P, I
AV:43
AV:44
AV:46
AV:47
AV:48
AV:49
AV:50
Alarm Log:
Error Code
1530
NONE
AV:51
Fault Code
4)
NONE
AV:52
PID Start
Speed
2083
Hz
x
AV:53
On Reference
Bandwidth
2084
%
x
AV:54
PID Propor-
tional Gain
2093
NONE
x
AV:55
PID Integral
Time
2094
S
x
Table 5.3 Analog Values
1)
Either AV:1 or AV:2 controls the frequency converter
reference. Only one of them can control the frequency
converter at a time and BV:2 decides which one.
2)
This value is not directly available in the frequency
converter. The value must be calculated as follows:
AV #3= Par. 16−13
Par. 4−14 ×100%
3)
This value is not directly available in the frequency
converter. The value must be calculated as follows:
AV #4= Par. 16−52
Par. 3−03 ×100%
4)
Frequency converter fault codes are transmitted as an
analog value in AV:51. The fault codes are mapped as
shown in
. The frequency converter alarm codes
are shown as well for comparison.
shows the mapping of the frequency converter
alarm codes and their mapping to the BACnet's fault
codes.
BACnet Objects
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
MG03O102 - Danfoss A/S
©
12/2013. All rights reserved.
15
5
5