6.2 Parameter Description
6.2.1 8-0* General Settings
8-01 Control Site
Option:
Function:
Select
[0] Digital and ctrl.word
for using
digital input and control word. Select
[1]
Digital
only to use digital inputs only. Select
[2] Control word only
to use control word
only. This parameter overrules settings in
parameter 8-50 Coasting Select
to
parameter 8-56 Preset Reference Select
[0]
*
Digital and
ctrl.word
Control by using both digital input and
control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword
only
Control by using control word only.
8-02 Control Source
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
Select the source of the control word.
[0]
None
[1]
*
FC Port
8-03 Control Timeout Time
Range:
Function:
1 s
*
[0.1 -
6500 s]
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it indicates
that the serial communication has stopped. The
function selected in
Control Time-out Function
is
carried out.
8-04 Control Timeout Function
Option: Function:
Select the timeout function. The time-out function is
activated when the control word fails to be updated
within the time period specified in
parameter 8-03 Control Timeout Time
[0]
*
Off
6.2.2 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
Select the protocol for the integrated RS-485
port.
8-30 Protocol
Option:
Function:
[0] FC
Communication according to the FC Protocol.
[2] Modbus
RTU
Communication according to the Modbus RTU
protocol.
[3] Metasys N2
Communication protocol. The N2 software
protocol is designed to accommodate the
unique properties each device may have.
[5] BACNet
8-31 Address
Range:
Function:
1
*
[ 0.0 - 247 ] Enter the address for the RS-485 port. Valid
range: 1-126 for FC-bus OR 1-247 for Modbus.
8-32 Baud Rate
Option:
Function:
Select the baud rate for the RS-485 port
Default refers to the FC Protocol. Changing
Protocol in
8-30 Protocol
may change the Baud
Rate.
Changing Protocol in
8-30 Protocol
may
change the Baud Rate.
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
Default setting for
•
Modbus RTU
•
BACnet
•
Metasys N2
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 Parity / Stop Bits
Option:
Function:
Parity and stop bits for the protocol
using the FC Port. For some of the
protocols, not all options are
available.
Default refers to the FC Protocol.
[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Function:
0.01 s
*
[ 0.0010 - 0.5
s]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is used for
Parameters
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
MG03O102 - Danfoss A/S
©