ID
Object_Name
Present_Value
Default
name
Writeable EEPROM Parameter
Bit
number
Writeable
Cmd.able EEPROM
Timeout
BV:0
Reserved for VFD profile
BV:1
RUN/STOP
Command
x
x
CTW=0x47C
+
Reversing
6 reverse 15 x
x
x
bit 15
BV:2
REF 1/REF 2
Select
x
x
Note 1
n/a
x
x
x
x
BV:3
Fault Reset
Command
x
x
CTW
7
x
BV:4
RUN/STOP
Monitor
x
x
STW
1
BV:5
OK/FAULT
Monitor
x
x
STW
3, 6, 7
BV:6
HAND/AUTO
Reference
x
x
16-95
1
BV:7
Reserved for VFD profile
BV:8
BV:9
BV:10
BV:11
BV:12
BV:13
BV:14
BV:15
BV:16
BV:17
BV:18
BV:19
BV:20
BV:21
Warning
x
x
STW
7
BV:22
Trip
x
x
STW
3
BV:23
Triplock
STW
6
BV:24
Coasting
CTW
3
x
x
x
BV:25
CW/CCW
CTW
15
x
x
x
BV:26
Jog
CTW
8
x
x
x
BV:27
Reset
CTW
7
x
x
x
BV:28
Reset KWh
Counter
1506
n/a
x
BV:29
Reset
Running
Hours
Counter
1507
n/a
x
BV:31
Speed =
reference
STW
8
BV:32
Bus control
STW
9
BV:33
Running
x
x
STW
11
BV:34
Ramp 1/
Ramp 2
CTW
9
x
x
Table 5.7 Binary Values
BACnet Objects
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
MG03O102 - Danfoss A/S
©
12/2013. All rights reserved.
17
5
5