4 System Configuration
4.1 Configuring BACnet
4.1.1 Initialisation Procedure
Parameter
Default Value
Setting for BACnet
8-01 Control Site
Digital and control word
Digital and control word
8-02 Control Source
FC RS-485
FC RS-485
8-03 Control Timeout Time
1 s
1)
8-04 Control Timeout Function
Off
1)
Table 4.1 General Settings
Parameter
Default Value
Setting for BACnet
8-30 Protocol
FC
BACnet
8-31 Address
1
1
3)
8-32 Baud Rate
9600
9600 baud
8-35 Minimum Response Delay
10 ms
10 ms
8-36 Maximum Response Delay
5,000 ms
5,000 ms
Table 4.2 FC Port Settings
1)
Depending on the application.
2)
Depending on the BMS system
3)
The address setting is dependent on the system. Each device connected to the BACnet MS/TP must have a unique address on this MS/TP
network. See also chapter 6.1 Parameter List.
Parameter
Default Value
Setting for BACnet
8-50 Coasting Select
Logic-or
Set according to the wiring of the application
8-52 DC Brake Select
Logic-or
Logic-or
8-53 Start Select
Logic-or
Logic-or
8-54 Reversing Select
Digital input
Digital input
8-55 Set-up Select
Logic-or
Logic-or
8-56 Preset Reference Select
Logic-or
Logic-or
Table 4.3 Digital/Bus Settings
Name
Default Value
Setting for BACnet
8-70 BACnet Device Instance
1
1
1)
8-72 MS/TP Max Masters
127
Dependent on the Number of Masters in the system
8-74 "I-Am" Service
At power up
At power up
8-75 Initialisation Password
“admin”
“admin”
Table 4.4 BACnet Settings
1)
The device instance setting is dependent on the system. Each device connected to the BACnet MS/TP must have a unique device instance in the
complete system.
System Configuration
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
12
MG03O102 - Danfoss A/S
©
12/2013. All rights reserved.