5.1.3 Multi-state Value Objects
ID
Object_Name
Present_Value
Timeout
Default name
Parameter
Bit number
Writeable
Cmd.able
MSV:0
Smart Logic Controller State 1638
n/a
MSV:1
Active Setup
CTW
13
x
x
x
Table 5.8 Multi-state Value
5.2 Frequency Converter Feedback to
Network
The BACnet option provides several output variables
(nvo’s) objects to the network, containing important
frequency converter-, motor- and I/O feedback data. The
BACnet option transmits bound network variables only and
sends feedback data when there is a change in value.
Influence of the digital input terminals upon the FC
Control Mode,
8-50 Coasting Select
to
8-56 Preset Reference
Select
The influence of the digital input terminals upon control of
the frequency converter can be programmed in
8-50 Coasting Select
to
8-56 Preset Reference Select
.
NOTICE
8-01 Control Site
overrules the settings in
8-50 Coasting
Select
to
8-56 Preset Reference Select
and Terminal 37,
Safe Stop overrules any parameter.
Each of the digital input signals can be programmed to
logic AND, logic OR, or to have no relation to the
corresponding bit in the control word. In this way a
specific control command i.e. stop/coast, can be initiated
by the fieldbus only, fieldbus AND Digital Input, or
Fieldbus OR Digital input terminal.
NOTICE
To control the frequency converter via BACnet, set
8-50 Coasting Select
to either
[1] Bus
or to
[2] Logic AND
and set
8-01 Control Site
to
[0] Digital and ctrl. word
or
[2]
Control word only
.
5.3 BIBBs
ReadProperty
Execute
WriteProperty
Execute
DeviceCommunicationControl
Execute
ReinitializeDevice
Execute
I-Am
Initiate
I-Have
Initiate
TimeSynchronization
Execute
Who-Has
Execute
Who-Is
Execute
Table 5.9 BIBBs
BACnet Objects
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
18
MG03O102 - Danfoss A/S
©
12/2013. All rights reserved.
5
5