Cable lengths and cross sections:
Max. motor cable length, screened/armoured cable
10 m
Max. motor cable length, unscreened/unarmoured cable
10 m
Max. cross section to motor, see next section.
Max. cross section to control wires, rigid wire
4.0 mm
2
/10 AWG
Max. cross section to control cables, flexible cable
2.5 mm
2
/12 AWG
Max. cross section to control cables, cable with ferrules
2.5 mm
2
/12 AWG
Max. cross section extra terminals for 24 V ext, T73 version, rigid cables
6.0 mm
2
/9 AWG
Max. cross section extra terminals for 24 V ext, T73 version, flexible cable
4 mm
2
/10 AWG
Max. cross section extra terminals for 24 V ext, T73 version, cable with ferrules
4 mm
2
/10 AWG
Max. cross section PE
10 mm
2
/7 AWG
Max. cross section external PE for T73 version
16 mm
2
/ 5 AWG
If UL/cUL is to be complied with, cable with temperature class 60/75°C must be used. Use copper wires only.
When complying with EN 55011 1A the motor cable must be screened/armoured. See EMC emission.
Control characteristics:
Frequency range
0.2 - 132 Hz, 1 - 1000 Hz
Resolution of output frequency
0.013 Hz, 0.2 - 1000 Hz
Repeat accuracy of
Precise start/stop
(terminals 18, 19)
≤
± 0.5 msec
System response time (terminals 18, 19, 27, 29, 33)
≤
26.6 msec
Speed control range (open loop)
1:15 of synchronous speed
Speed control range (open loop) <1.1 kW
approximately 1:10 of synchronous speed (motor dependent)
Speed control range (closed loop)
1:120 of synchronous speed
Speed accuracy (open loop) <1.1 kW
150 - 3600 rpm: Max. error of ±23 rpm
Speed accuracy (open loop) >0.75 kW
90 - 3600 rpm: Max. error of ±23 rpm
Speed accuracy (closed loop)
30 - 3600 rpm: Max. error of ±7.5 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure
IP 66, TYPE 4x (indoor)
Enclosure T73 version
IP 65, TYPE 12
Vibration test
1.0 g
Max. relative humidity
95%
see Air humidity in the Design Guide
Ambient temperature (FCD 335 max. 35 °C)
Max. 40 °C (24-hour average max. 35 °C)
Derating for ambient temperature, see special conditions in the Design Guide
Min. ambient temperature during full-scale operation
0 °C
Min. ambient temperature at reduced performance
- 10 °C
Temperature during storage/transport
-25 - +65/70 °C
Max. altitude above sea level
1000 m
Derating for air pressure, see special conditions in the Design Guide
EMC standards used, Emission
EN 50081-1-2, EN 61800-3, EN 55011
EMC standards used, immunity
EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions in the Design Guide
Safeguards:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the power module ensures that the frequency converter cuts out if the temperature reaches 100 °C. An overload
temperature cannot be reset until the temperature of the power module is below 70 °C.
•
The frequency converter is protected against short-circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter will cut out.
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate circuit voltage is too low or too
high.
•
The frequency converter is protected against earth fault on motor terminals U, V, W.
VLT® Decentral FCD