Parameter
Setting
Notes
13-40 Logic Rule Boolean 1 [0]
[37] Digital
Input DI32
13-42 Logic Rule Boolean 2 [0] [2] Running
13-41 Logic Rule Operator 1
[0]
[3] AND
NOT
13-40 Logic Rule Boolean 1 [1]
[37] Digital
Input DI32
13-42 Logic Rule Boolean 2 [1] [2] Running
13-41 Logic Rule Operator 1
[1]
[1] AND
[26]
Logicrule 0
Output from 13-41
[0]
[27]
Logicrule 1
Output from 13-41
[1]
[94] RS
Flipflop 0
Output from
evaluating 13-15
and 13-16
13-52 SL Controller Action [0] [22] Run
[27]
Logicrule 1
13-52 SL Controller Action [1] [24] Stop
Table 6.10
13-15 RS-FF Operand S
Option:
Function:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
13-15 RS-FF Operand S
Option:
Function:
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
Ok key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[75]
Start command given
[76]
Digital input x30/2
[77]
Digital input x30/3
[78]
Digital input x30/4
[79]
Digital input x46/1
[80]
Digital input x46/3
[81]
Digital input x46/5
[82]
Digital input x46/7
[83]
Digital input x46/9
[84]
Digital input x46/11
[85]
Digital input x46/13
[90]
ATEX ETR cur. warning
[91]
ATEX ETR cur. alarm
[92]
ATEX ETR freq. warning
[93]
ATEX ETR freq. alarm
[94]
RS Flipflop 0
[95]
RS Flipflop 1
[96]
RS Flipflop 2
Parameter Descriptions
Operating Instructions VLT
®