6.7 Parameters: 6-** Analog In/Out
Parameter group for configuration of the analog input and
output.
6.7.1 6-0* Analog In/Out Mode
Parameter group for setting up the analog In/Out configu-
ration.
The frequency converter is equipped with 2 analog inputs:
Terminal 53 and 54. The analog inputs on the frequency
converter can freely be allocated to either voltage (-10 V to
+10 V) or current input (0/4 to 20 mA).
6-00 Live Zero Timeout Time
Range:
Function:
10 s
*
[1 -
99 s]
Enter the Live Zero Time-out time period. Live
Zero Time-out Time is active for analog inputs, i.e.
terminal 53 or terminal 54, used as reference or
feedback sources. If the reference signal value
associated with the selected current input falls
below 50% of the value set in
6-10 Terminal 53
Low Voltage
,
6-12 Terminal 53 Low Current
,
6-20 Terminal 54 Low Voltage
or
6-22 Terminal 54
Low Current
for a time period longer than the time
set in
, the function
selected in
6-01 Live Zero Timeout Function
will be
activated.
6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function set
in
6-01 Live Zero Timeout Function
will be
activated if the input signal on terminal 53 or
54 is below 50% of the value in
6-10 Terminal
53 Low Voltage
,
6-12 Terminal 53 Low Current
,
6-20 Terminal 54 Low Voltage
or
6-22 Terminal
54 Low Current
for a time period defined in
. If several time-
outs occur simultaneously, the frequency
converter prioritises the time-out functions as
follows:
1.
6-01 Live Zero Timeout Function
2.
8-04 Control Word Timeout Function
[1]
Freeze
Output
Frozen at the present value
[0]
*
Off
[1]
Freeze
output
Frozen at the present value
[2]
Stop
Overruled to stop
[3]
Jogging
Overruled to jog speed
[4]
Max. speed Overruled to max. speed
[5]
Stop and
trip
Overruled to stop with subsequent trip
6.7.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for
analog input 1 (terminal 53).
NOTE
Analog input 53 is preset for usage with “open loop”
control on 0-10 V. Terminal 54 is preset for “Process Loop”
control using a pressure sensor AKS with a pressure range
of -1 : 12 bar.
6-10 Terminal 53 Low Voltage
Range:
Function:
0.00V
*
[-10.0 - par.
6-11]
This analog input scaling value should
correspond to the minimum reference
value, set in
3-02 Minimum Reference
.
6-11 Terminal 53 High Voltage
Range:
Function:
10.00V
*
[6-10 to 10 V] This analog input scaling value should
correspond to the maximum reference
value, set in
3-03 Maximum Reference
.
6-12 Terminal 53 Low Current
Range:
Function:
4.0mA
*
[0.0 to par. 6-13
mA]
This reference signal should
correspond to the minimum
reference value, set in
3-02 Minimum
Reference
.
6-13 Terminal 53 High Current
Range:
Function:
20.0mA
*
[6-12 to 20 mA] This reference signal should
correspond to the maximum
reference value, set in
3-02 Minimum
Reference
.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
Size related
*
[Enter the analog input scaling value
that corresponds to the low voltage/low
current set in
6-10 Terminal 53 Low
Voltage
and
6-12 Terminal 53 Low
Current
.]
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Size related
*
[]
Enter the analog input scaling value that
corresponds to the maximum reference
feedback value set in
6-11 Terminal 53 High
Voltage
and
6-13 Terminal 53 High Current
.
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor
69