The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from
the supplier voltage (PELV).
Control Card, USB Serial Communication
USB standard
1.1 (Full speed)
USB plug
USB type B device plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB
ground connection is not galvanically isolated from protection earth. Use only isolated laptop as PC connection to the USB
connector on the frequency converter drive
Relay Outputs
Programmable relay outputs
2
Relay 01 Terminal number
1-3 (break),1-2 (make)
Max. terminal load (AC-1)1) on 1-3 (NC), 1-2 (NO) (Resistive load)
240 V AC, 2 A
Max. terminal load (AC-15)1) (Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Max. terminal load (DC-1)1) on 1-2 (NO), 1-3 (NC) (Resistive load)
60 V DC, 1 A
Max. terminal load (DC-13)1) (Inductive load)
24 V DC, 0.1 A
Relay 02 (CDS302 only) Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)1) on 4-5 (NO) (Resistive load)
400 V AC, 2 A
Max. terminal load (AC-15)1) on 4-5 (NO) (Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Max. terminal load (DC-1)1) on 4-5 (NO) (Resistive load)
80 V DC, 2 A
Surroundings
Enclosure ≤ enclosure type A
IP20, IP55
Enclosure ≥ enclosure type A, B
IP21, IP55
Enclosure kit available ≤ enclosure type A
IP21/TYPE 1/IP 4X top
Vibration test
1.0 g
Max. relative humidity
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated
class 3C2
Aggressive environment (IEC 721-3-3), coated
class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Max. 50 °C
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation
0 °C
Minimum ambient temperature at reduced performance
- 10 °C
Temperature during storage/transport
-25 - +65/70 °C
Maximum altitude above sea level without derating
1000 m
Maximum altitude above sea level with derating
3000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
General Specifications
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®