5-13 Terminal 29 Digital Input
Option:
Function:
[14]
*
Jog
[60]
Counter A (up)
[61]
Counter A (down)
[63]
Counter B (up)
[64]
Counter B (down)
5-14 Terminal 32 Digital Input
Option:
Function:
Select the function from the available digital
input range.
[0]
*
No operation Functions are described under
5-1* Digital
Inputs
5-15 Terminal 33 Digital Input
Option:
Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in
Smart Logic Control functions.
[0]
*
No operation Functions are described under
5-1* Digital
Inputs
6.6.4 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
5-01 Terminal 27 Mode
, and set the I/O
function for terminal 29 in
5-02 Terminal 29 Mode
. Digital
outputs appear if
5-01 Terminal 27 Mode
or
5-02 Terminal
29 Mode
are set to output.
NOTE
These parameters cannot be adjusted while the motor is
running.
NOTE
Only for activating 24 V DC devices − restricted use for
relays.
The digital outputs can be programmed
with these functions:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control board receives supply
voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3]
Drive ready /
remote control
The frequency converter is ready for
operation and is in Auto On mode.
[4]
Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is
been given (start/disable). There are no
warnings.
[5]
Running
The motor is running.
[6]
Running / no
warning
The output speed is higher than the
speed set in
1-81 Min Speed for Function
at Stop [RPM]
. The motor is running and
there are no warnings.
[7]
Run on
reference / no
warning
The motor runs at reference speed.
[8]
Run in range /
no warning
The motor runs in speed range.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque limit The torque limit set in
4-16 Torque Limit
Motor Mode
or
1-17 Voltage filter time
const.
has been exceeded.
[12]
Out of current
range
The motor current is outside the range
set in
4-18 Current Limit
.
[13]
Below current,
low
The motor current is lower than set in
.
[14]
Above current,
high
The motor current is higher than set in
.
[15]
Out of speed
range
The output speed is outside the range set
in
and
4-53 Warning Speed High
.
[16]
Below speed,
low
The output speed is lower than the
setting in
[17]
Above speed,
high
The output speed is higher than the
setting in
4-53 Warning Speed High
.
[18]
Out of
feedback range
The feedback is outside the range set in
and
[19]
Below
feedback low
The feedback is below the limit set in
Warning
Feedback Low.
[20]
Above
feedback high
The feedback is above the limit set in
Warning
Feedback High
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[25]
Reverse
Reversing. Logic ‘1’ =
relay activated, 24 V
DC when CW rotation of the motor. Logic
‘0’ = relay not activated, no signal, when
CCW rotation of the motor.
[26]
Bus OK
Active communication (no time-out) via
the serial communication port.
[27]
Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and
is at the torque limit, the signal is Logic
‘0’.
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303