Mains Supply 3 x 525- 690V AC
FC 302
P30K
P37K
P45K
P55K
P75K
High/ Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at 550V
[kW]
22
30
30
37
37
45
45
55
55
75
Typical Shaft output at 575V
[HP]
30
40
40
50
50
60
60
75
75
100
Typical Shaft output at 690V
[kW]
30
37
37
45
45
55
55
75
75
90
Enclosure IP21, 55
C2
C2
C2
C2
C2
Output current
Continuous
(3 x 525-550V) [A]
36
43
43
54
54
65
65
87
87
105
Intermittent (60 sec
overload)
(3 x 525-550V) [A]
54
47.3
64.5
59.4
81
71.5
97.5
95.7
130.5
115.5
Continuous
(3 x 551-690V) [A]
34
41
41
52
52
62
62
83
83
100
Intermittent (60 sec
overload)
(3 x 551-690V) [A]
51
45.1
61.5
57.2
78
68.2
93
91.3
124.5
110
Continuous KVA
(at 550V) [KVA]
34.3
41.0
41.0
51.4
51.4
61.9
61.9
82.9
82.9
100.0
Continuous KVA
(at 575V) [KVA]
33.9
40.8
40.8
51.8
51.8
61.7
61.7
82.7
82.7
99.6
Continuous KVA
(at 690V) [KVA]
40.6
49.0
49.0
62.1
62.1
74.1
74.1
99.2
99.2
119.5
Max. input current
Continuous
(at 550V) [A]
36
49
49
59
59
71
71
87
87
99
Continuous
(at 575V) [A]
54
53.9
72
64.9
87
78.1
105
95.7
129
108.9
Additional specifications
Max. cable size, mains,
motor, load share and brake
[mm
2
(AWG)]
95 (4/0)
Estimated power loss
at rated max. load [W]
4)
480
592
720
880
1200
Weight,
enclosure IP21, IP55 [kg]
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.98
For fuse ratings, see
1) High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to variety
in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the
power loss in the frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W
to the losses. (Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed
for (+/-5%).
Specifications
VLT
®
AutomationDrive Operating
Instructions
70
MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
10