The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to parameter group
5-**
Digital In/Out
and press [OK].
2.
Scroll to parameter group 5-1*
Digital Inputs
and
press [OK].
3.
Scroll to
5-10 Terminal 18 Digital Input
. Press [OK] to
access function choices. The default setting
Start
is
shown.
5.4 International/North American Default
Parameter Settings
Setting
0-03 Regional Settings
to [0]
International
or [1]
North
America
changes the default settings for some parameters.
lists those parameters that are effected.
Parameter
International
default parameter
value
North American
default parameter
value
0-03 Regional
Settings
International
North America
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage
230V/400V/575V
208V/460V/575V
Parameter
International
default parameter
value
North American
default parameter
value
1-23 Motor
Frequency
50Hz
60Hz
3-03 Maximum
Reference
50Hz
60Hz
3-04 Reference
Function
Sum
External/Preset
4-13 Motor Speed
High Limit [RPM]
See Note 3 and 5
1500RPM
1800RPM
4-14 Motor Speed
High Limit [Hz]
See Note 4
50Hz
60Hz
4-19 Max Output
Frequency
132Hz
120Hz
4-53 Warning Speed
High
1500RPM
1800RPM
5-12 Terminal 27
Digital Input
Coast inverse
External interlock
5-40 Function Relay No operation
No alarm
6-15 Terminal 53
High Ref./Feedb.
Value
50
60
6-50 Terminal 42
Output
No operation
Speed 4-20mA
14-20 Reset Mode
Manual reset
Infinite auto reset
Table 5.1 International/North American Default Parameter Settings
Note 1:
1-20 Motor Power [kW]
is only visible when
0-03 Regional Settings
is set to [0]
International
.
Note 2:
1-21 Motor Power [HP]
, is only visible when
0-03 Regional Settings
is set to [1]
North America
.
Note 3: This parameter is only visible when
0-02 Motor Speed
Unit
is set to [0]
RPM
.
Note 4: This parameter is only visible when
0-02 Motor Speed
Unit
is set to [1]
Hz
.
Note 5: The default value depends on the number of motor
poles. For a 4 poled motor the international default value is
1500RPM and for a 2 poled motor 3000RPM. The
corresponding values for North America is 1800 and
3600RPM, respectively.
Changes made to default settings are stored and available
for viewing in the quick menu along with any programming
entered into parameters.
1.
Press [Quick Menu].
2.
Scroll to Q5
Changes Made
and press [OK].
About Frequency Converter P...
VLT
®
AutomationDrive Operating
Instructions
MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
33
5