4.2.1 Uploading Data to the LCP
1.
Press [OFF] to stop the motor before uploading or
downloading data.
2.
Go to
0-50 LCP Copy
.
3.
Press [OK].
4.
Select
All to LCP
.
5.
Press [OK]. A progress bar shows the uploading
process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.2.2 Downloading Data from the LCP
1.
Press [OFF] to stop the motor before uploading or
downloading data.
2.
Go to
0-50 LCP Copy
.
3.
Press [OK].
4.
Select
All from LCP
.
5.
Press [OK]. A progress bar shows the downloading
process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.3 Restoring
Default
Settings
CAUTION
Initialisation restores the unit to factory default settings. Any
programming, motor data, localization, and monitoring
records will be lost. Uploading data to the LCP provides a
backup prior to initialisation.
Restoring the frequency converter parameter settings back
to default values is done by initialisation of the frequency
converter. Initialisation can be through
14-22 Operation Mode
or manually.
•
Initialisation using
14-22 Operation Mode
does not
change frequency converter data such as operating
hours, serial communication selections, personal
menu settings, fault log, alarm log, and other
monitoring functions
•
Using
14-22 Operation Mode
is generally
recommended
•
Manual initialisation erases all motor,
programming, localization, and monitoring data
and restores factory default settings
4.3.1 Recommended Initialisation
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
14-22 Operation Mode
.
3.
Press [OK].
4.
Scroll to
Initialisation
.
5.
Press [OK].
6.
Remove power to the unit and wait for the display
to turn off.
7.
Apply power to the unit.
Default parameter settings are restored during start up. This
may take slightly longer than normal.
8.
Alarm 80 is displayed.
9.
Press [Reset] to return to operation mode.
4.3.2 Manual Initialisation
1.
Remove power to the unit and wait for the display
to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
Factory default parameter settings are restored during start
up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information
•
15-00 Operating Hours
•
15-03 Power Up's
•
15-04 Over Temp's
•
15-05 Over Volt's