Mains Supply 3 x 380 - 500 V AC (FC 302), 3 x 380 - 480V AC (FC 301)
FC 301/FC 302
P30K
P37K
P45K
P55K
P75K
High/ Normal Load
1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output [kW]
30
37
37
45
45
55
55
75
75
90
Enclosure IP20
B4
C3
C3
C4
C4
Enclosure IP21
C1
C1
C1
C2
C2
Enclosure IP55, 66
C1
C1
C1
C2
C2
Output current
Continuous
(3 x 380-440V) [A]
61
73
73
90
90
106
106
147
147
177
Intermittent (60 sec.
overload)
(3 x 380-440V) [A]
91.5
80.3
110
99
135
117
159
162
221
195
Continuous
(3 x 441-500V) [A]
52
65
65
80
80
105
105
130
130
160
Intermittent (60 sec
overload)
(3 x 441-500V) [A]
78
71.5
97.5
88
120
116
158
143
195
176
Continuous kVA
(400V AC) [kVA]
42.3
50.6
50.6
62.4
62.4
73.4
73.4
102
102
123
Continuous kVA
(460V AC) [kVA]
51.8
63.7
83.7
104
128
Max. input current
Continuous
(3 x 380-440V) [A]
55
66
66
82
82
96
96
133
133
161
Intermittent (60 sec
overload)
(3 x 380-440V) [A]
82.5
72.6
99
90.2
123
106
144
146
200
177
Continuous
(3 x 441-500V) [A]
47
59
59
73
73
95
95
118
118
145
Intermittent (60 sec
overload)
(3 x 441-500V) [A]
70.5
64.9
88.5
80.3
110
105
143
130
177
160
Additional specifications
Max. cable size IP20, mains
and motor [mm
2
(AWG
2)
)]
35 (2)
50 (1)
50 (1)
95 (4/0)
150 (300mcm)
Max. cable size IP20, load
share and brake [mm
2
(AWG
2)
)]
35 (2)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
Max. cable size, IP21/55/66
[mm
2
(AWG
2)
)]
90 (3/0)
90 (3/0)
90 (3/0)
120 (4/0)
120 (4/0)
Max cable size with mains
disconnect [mm
2
(AWG
2)
)]
35 (2)
70 (3/0)
150 (300mcm)
Estimated power loss
at rated max. load [W]
4)
570
698
697
843
891
1083
1022
1384
1232
1474
Weight,
enclosure IP21, IP55, 66 [kg]
45
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.99
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
65
10
10