Enclosure
FC 300 Power
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level
Size
[kW]
Moeller
[A]
A2
0-75-4.0
gG-10
gG-25
PKZM0-25
25
A3
5.5-7.5
gG-10 (5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
B3
11-15
gG-25 (11)
gG-32 (15)
gG-63
PKZM4-50
50
B4
18.5-30
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-125
NZMB1-A100
100
C3
37-45
gG-63 (37)
gG-100 (45)
gG-150
NZMB2-A200
150
C4
55-75
aR-160 (55)
aR-200 (75)
aR-250
NZMB2-A250
250
A5
0.75-7.5
gG-10 (0.75-5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
B1
11-18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-80
PKZM4-63
63
B2
22-30
gG-50 (22)
gG-63 (30)
gG-100
NZMB1-A100
100
C1
37-55
gG-63 (37)
gG-100 (45)
aR-160 (55)
gG-160 (37-45)
aR-250 (55)
NZMB2-A200
160
C2
75
aR-200 (75)
aR-250
NZMB2-A250
250
Table 10.3 525-600V, Frame Sizes A, B, and C
Enclosure
FC 300 Power
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level
Size
[kW]
Moeller
[A]
B2
11
15
18
22
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63
-
-
C2
30
37
45
55
75
gG-63 (30)
gG-63 (37)
gG-80 (45)
gG-100 (55)
gG-125 (75)
gG-80 (30)
gG-100 (37)
gG-125 (45)
gG-160 (55-75)
-
-
D
37-315
gG-125 (37)
gG-160 (45)
gG-200 (55-75)
aR-250 (90)
aR-315 (110)
aR-350 (132-160)
aR-400 (200)
aR-500 (250)
aR-550 (315)
gG-125 (37)
gG-160 (45)
gG-200 (55-75)
aR-250 (90)
aR-315 (110)
aR-350 (132-160)
aR-400 (200)
aR-500 (250)
aR-550 (315)
-
-
E
355-560
aR-700 (355-400)
aR-900 (500-560)
aR-700 (355-400)
aR-900 (500-560)
-
-
F
630-1200
aR-1600 (630-900)
aR-2000 (1000)
aR-2500 (1200)
aR-1600 (630-900)
aR-2000 (1000)
aR-2500 (1200)
-
-
Table 10.4 525-690V, Frame Sizes B, C, D, E, and F
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
79