Recommended max. fuse
FC 300
Bussmann
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
[kW]
Type JFHR2
2)
JFHR2
JFHR2
4)
J
0.25–0.37
FWX-5
-
-
HSJ-6
0.55–1.1
FWX-10
-
-
HSJ-10
1.5
FWX-15
-
-
HSJ-15
2.2
FWX-20
-
-
HSJ-20
3.0
FWX-25
-
-
HSJ-25
3.7
FWX-30
-
-
HSJ-30
5.5
FWX-50
-
-
HSJ-50
7.5
FWX-60
-
-
HSJ-60
11
FWX-80
-
-
HSJ-80
15–18.5
FWX-125
-
-
HSJ-125
22
FWX-150
L25S-150
A25X-150
HSJ-150
30
FWX-200
L25S-200
A25X-200
HSJ-200
37
FWX-250
L25S-250
A25X-250
HSJ-250
Table 10.7 200–240V, Frame Sizes A, B, and C
1) KTS fuses from Bussmann may substitute KTN for 240V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute FWX for 240V adjustable frequency drives.
3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240V adjustable frequency drives.
Recommended max. fuse
FC 300
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
[kW]
Type RK1
Type J
Type T
Type CC
Type CC
Type CC
0.37–1.1
KTS-R-6
JKS-6
JJS-6
FNQ-R-6
KTK-R-6
LP-CC-6
1.5–2.2
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3
KTS-R-15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
4
KTS-R-20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11
KTS-R-40
JKS-40
JJS-40
-
-
-
15
KTS-R-50
JKS-50
JJS-50
-
-
-
18
KTS-R-60
JKS-60
JJS-60
-
-
-
22
KTS-R-80
JKS-80
JJS-80
-
-
-
30
KTS-R-100
JKS-100
JJS-100
-
-
-
37
KTS-R-125
JKS-125
JJS-125
-
-
-
45
KTS-R-150
JKS-150
JJS-150
-
-
-
55
KTS-R-200
JKS-200
JJS-200
-
-
-
75
KTS-R-250
JKS-250
JJS-250
-
-
-
Table 10.8 380–500V, Frame Sizes A, B, and C
Specifications
VLT
®
AutomationDrive Instruction
Manual
10-22
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
10
10