Terminal description
Terminal Parameter
Default
setting
Description
27
5-12
[2] Coast
inverse
Selectable for either
digital input or
output. Default setting
is input.
29
5-13
[14] JOG
20
-
Common for digital
inputs and 0V
potential for 24V
supply.
37
-
Safe Torque
Off (STO)
Safe input. Used for
STO.
Analog inputs/outputs
39
-
Common for analog
output
42
6-50
[0] No
operation
Programmable analog
output. The analog
signal is 0–20mA or
4–20mA at a
maximum of 500
Ω
50
-
+10V DC
10V DC analog supply
voltage. 15mA
maximum commonly
used for potenti-
ometer or thermistor.
53
6-1
Reference
Analog input.
Selectable for voltage
or current. Switches
A53 and A54 select
mA or V.
54
6-2
Feedback
55
-
Common for analog
input
Terminal description
Terminal Parameter
Default
setting
Description
Serial communication
61
-
Integrated RC filter for
cable screen. ONLY for
connecting the shield
when experiencing
EMC problems.
68 (+)
8-3
RS-485 Interface. A
control card switch is
provided for
termination resistance.
69 (-)
8-3
Relays
Terminal description
Terminal Parameter
Default
setting
Description
01, 02, 03
5-40 [0]
[0] No
operation
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.
04, 05, 06
5-40 [1]
[0] No
operation
Table 2.3 Terminal Description
2.4.5.3 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
Adjustable frequency drive for ease of installation, as
shown in
.
1.
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in
.
2.
Insert the bared control wire into the contact.
3.
Remove the screwdriver to fasten the control wire
into the contact.
4.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
See
10.1 Power-dependent Specifications
for control terminal
wiring sizes.
See
for typical control wiring
connections.
2
1
10 mm
130BA310.10
12 13
18
19
27
29
32
33
Figure 2.13 Connecting Control Wiring
2.4.5.4 Using Shielded Control Cables
Correct shielding
The preferred method in most cases is to secure control
and serial communication cables with shielding clamps
provided at both ends to ensure best possible high
frequency cable contact.
If the ground potential between the adjustable frequency
drive and the PLC is different, electric noise may occur that
will disturb the entire system. Solve this problem by fitting
Installation
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
2-9
2
2