2.
Scroll to parameter group 5-1*
Digital Inputs
and
press [OK].
130B
T769.10
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
14.7% 0.00A 1(1)
Digital In/Out
5-**
3.
Scroll to
5-10 Terminal 18 Digital Input
. Press [OK]
to access function choices. The default setting
Start
is shown.
5-1*
130B
T770.10
5-10 Terminal 18 Digital
Input
[
8
]] Start
14.7% 0.00A 1(1)
Digital Inputs
5.4 International/North American Default
Parameter Settings
Setting
0-03 Regional Settings
to [0]
International
or [1]
North America
changes the default settings for some
parameters.
lists those parameters that are
effected.
Parameter
International
default parameter
value
North American
default parameter
value
0-03 Regional
Settings
International
North America
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage 230V/400V/575V
208V/460V/575V
1-23 Motor
Frequency
50Hz
60Hz
3-03 Maximum
Reference
50Hz
60Hz
3-04 Reference
Function
Sum
External/Preset
4-13 Motor Speed
High Limit [RPM]
See Note 3 and 5
1500 RPM
1800 RPM
Parameter
International
default parameter
value
North American
default parameter
value
4-14 Motor Speed
High Limit [Hz]
See Note 4
50Hz
60Hz
4-19 Max Output
Frequency
132Hz
120Hz
4-53 Warning Speed
High
1500 RPM
1800 RPM
5-12 Terminal 27
Digital Input
Coast inverse
External interlock
5-40 Function Relay No operation
No alarm
6-15 Terminal 53
High Ref./Feedb.
Value
50
60
6-50 Terminal 42
Output
No operation
Speed 4–20 mA
14-20 Reset Mode
Manual reset
Infinite auto reset
Table 5.1 International/North American Default Parameter Settings
Note 1: 1-20 Motor Power [kW] is only visible when 0-03 Regional
Settings is set to [0] International.
Note 2: 1-21 Motor Power [HP] , is only visible when 0-03 Regional
Settings is set to [1] North America.
Note 3: This parameter is only visible when 0-02 Motor Speed Unit is
set to [0] RPM.
Note 4: This parameter is only visible when 0-02 Motor Speed Unit is
set to [1] Hz.
Note 5: The default value depends on the number of motor poles. For
a 4-poled motor, the international default value is 1500 RPM and for
a 2-poled motor, 3000 RPM. The corresponding values for North
America is 1800 RPM and 3600 RPM, respectively.
Changes made to default settings are stored and available
for viewing in the quick menu along with any
programming entered into parameters.
1.
Press [Quick Menu].
2.
Scroll to Q5 Changes Made and press [OK].
130BB849.10
Q1 M y P ersonal M enu
Q2 Quick S etup
Q5 Changes M ade
Q6 L ogg ings
25.9% 0.00A 1(1)
Quick M enus
About Adjustable Frequency ...
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
5-3
5
5