Recommended max. fuse
FC 302
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
[kW]
Type RK1
Type J
Type T
Type CC
Type CC
Type CC
0.75–1.1
KTS-R-5
JKS-5
JJS-6
FNQ-R-5
KTK-R-5
LP-CC-5
1.5–2.2
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3
KTS-R15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
4
KTS-R20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11
KTS-R-35
JKS-35
JJS-35
-
-
-
15
KTS-R-45
JKS-45
JJS-45
-
-
-
18
KTS-R-50
JKS-50
JJS-50
-
-
-
22
KTS-R-60
JKS-60
JJS-60
-
-
-
30
KTS-R-80
JKS-80
JJS-80
-
-
-
37
KTS-R-100
JKS-100
JJS-100
-
-
-
45
KTS-R-125
JKS-125
JJS-125
-
-
-
55
KTS-R-150
JKS-150
JJS-150
-
-
-
75
KTS-R-175
JKS-175
JJS-175
-
-
-
Table 10.11 525–600V, Frame Sizes A, B, and C
Recommended max. fuse
FC 302
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
[kW]
Type RK1
Type RK1
Type RK1
J
0.75–1.1
5017906-005
KLS-R-005
A6K-5-R
HSJ-6
1.5–2.2
5017906-010
KLS-R-010
A6K-10-R
HSJ-10
3
5017906-016
KLS-R-015
A6K-15-R
HSJ-15
4
5017906-020
KLS-R-020
A6K-20-R
HSJ-20
5.5
5017906-025
KLS-R-025
A6K-25-R
HSJ-25
7.5
5017906-030
KLS-R-030
A6K-30-R
HSJ-30
11
5014006-040
KLS-R-035
A6K-35-R
HSJ-35
15
5014006-050
KLS-R-045
A6K-45-R
HSJ-45
18
5014006-050
KLS-R-050
A6K-50-R
HSJ-50
22
5014006-063
KLS-R-060
A6K-60-R
HSJ-60
30
5014006-080
KLS-R-075
A6K-80-R
HSJ-80
37
5014006-100
KLS-R-100
A6K-100-R
HSJ-100
45
2028220-125
KLS-R-125
A6K-125-R
HSJ-125
55
2028220-150
KLS-R-150
A6K-150-R
HSJ-150
75
2028220-200
KLS-R-175
A6K-175-R
HSJ-175
Table 10.12 525–600V, Frame Sizes A, B, and C
1)
170M fuses shown from Bussmann use the -/80 visual indicator. –TN/80 Type T, -/110 or TN/110 Type T indicator
fuses of the same size and amperage may be substituted.
Specifications
VLT
®
AutomationDrive Instruction
Manual
10-24
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
10
10