Recommended max. fuse
FC 302
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
[kW]
Type RK1
Type RK1
Type CC
Type RK1
0.37–1.1
5017906-006
KLS-R-6
ATM-R-6
A6K-6-R
1.5–2.2
5017906-010
KLS-R-10
ATM-R-10
A6K-10-R
3
5017906-016
KLS-R-15
ATM-R-15
A6K-15-R
4
5017906-020
KLS-R-20
ATM-R-20
A6K-20-R
5.5
5017906-025
KLS-R-25
ATM-R-25
A6K-25-R
7.5
5012406-032
KLS-R-30
ATM-R-30
A6K-30-R
11
5014006-040
KLS-R-40
-
A6K-40-R
15
5014006-050
KLS-R-50
-
A6K-50-R
18
5014006-063
KLS-R-60
-
A6K-60-R
22
2028220-100
KLS-R-80
-
A6K-80-R
30
2028220-125
KLS-R-100
-
A6K-100-R
37
2028220-125
KLS-R-125
-
A6K-125-R
45
2028220-160
KLS-R-150
-
A6K-150-R
55
2028220-200
KLS-R-200
-
A6K-200-R
75
2028220-250
KLS-R-250
-
A6K-250-R
Table 10.9 380–500V, Frame Sizes A, B, and C
Recommended max. fuse
FC 302
Bussmann
Ferraz-Shawmut
Ferraz-Shawmut
Littel fuse
[kW]
JFHR2
J
JFHR2
1)
JFHR2
0.37–1.1
FWH-6
HSJ-6
-
-
1.5–2.2
FWH-10
HSJ-10
-
-
3
FWH-15
HSJ-15
-
-
4
FWH-20
HSJ-20
-
-
5.5
FWH-25
HSJ-25
-
-
7.5
FWH-30
HSJ-30
-
-
11
FWH-40
HSJ-40
-
-
15
FWH-50
HSJ-50
-
-
18
FWH-60
HSJ-60
-
-
22
FWH-80
HSJ-80
-
-
30
FWH-100
HSJ-100
-
-
37
FWH-125
HSJ-125
-
-
45
FWH-150
HSJ-150
-
-
55
FWH-200
HSJ-200
A50-P-225
L50-S-225
75
FWH-250
HSJ-250
A50-P-250
L50-S-250
Table 10.10 380–500V, Frame Sizes A, B, and C
1) Ferraz-Shawmut A50QS fuses may substitute for A50P fuses.
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
10-23
10