3 Product Overview
3.1 Intended Use
The drive is an electronic motor controller that converts AC mains input into a variable AC waveform output. The frequency
and voltage of the output are regulated to control the motor speed or torque. The drive is designed to:
•
Regulate motor speed in response to system feedback or to remote commands from external controllers.
•
Monitor system and motor status.
•
Provide motor overload protection.
The drive is designed for industrial and commercial environments in accordance with local laws and standards. Depending
on configuration, the drive can be used in standalone applications or form part of a larger system or installation.
NOTICE
In a residential environment, this product can cause radio interference, in which case supplementary mitigation
measures can be required.
Foreseeable misuse
Do not use the drive in applications which are non-compliant with specified operating conditions and environments. Ensure
compliance with the conditions specified in
.
3.2 Power Ratings, Weight, and Dimensions
For enclosure sizes and power ratings of the drives, refer to
. For more dimensions, see
Enclosure size
D1h
D2h
D3h
D4h
D3h
D4h
Rated power [kW]
45–55 kW
(200–240 V)
90–132 kW
(380–500 V)
90–132 kW
(525–690 V)
75–150 kW
(200–240 V)
160–250 kW
(380–500 V)
160–315 kW
(525–690 V)
45–55 kW
(200–240 V)
90–132 kW
(380–500 V)
37–132 kW
(525–690 V)
75–150 kW
(200–240 V)
160–250 kW
(380–500 V)
160–315 kW
(525–690 V)
With regen or load share terminals
1)
IP
NEMA
21/54
Type 1/12
21/54
Type 1/12
20
Chassis
20
Chassis
20
Chassis
20
Chassis
Shipping
dimensions [mm
(inch)]
Height
587 (23)
587 (23)
587 (23)
587 (23)
587 (23)
587 (23)
Width
997 (39)
1170 (46)
997 (39)
1170 (46)
1230 (48)
1430 (56)
Depth
460 (18)
535 (21)
460 (18)
535 (21)
460 (18)
535 (21)
Drive
dimensions [mm
(inch)]
Height
893 (35)
1099 (43)
909 (36)
1122 (44)
1004 (40)
1268 (50)
Width
325 (13)
420 (17)
250 (10)
350 (14)
250 (10)
350 (14)
Depth
378 (15)
378 (15)
375 (15)
375 (15)
375 (15)
375 (15)
Maximum weight [kg (lb)]
98 (216)
164 (362)
98 (216)
164 (362)
108 (238)
179 (395)
Table 3.1 Power Ratings, Weight, and Dimensions, Enclosure Sizes D1h–D4h
1) Regen, load share, and brake terminal options are not available for 200–240 V drives.
Product Overview
Operating Guide
MG34U502
Danfoss A/S © 09/2018 All rights reserved.
7
3
3
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......