Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB930.10
Function
Setting
Parameter 1-29
Automatic Motor
Adaptation
(AMA)
[1] Enable
complete AMA
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
*=Default value
Notes/comments:
Set
parameter group 1-2* Motor
Data
according to motor
nameplate.
Table 8.2 Wiring Configuration for AMA without
T27 Connected
8.3 Wiring Configurations for Analog Speed
Reference
Parameters
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
0 – 10 V
+
-
e30bb926.11
FC
Function
Setting
Parameter 6-10
Terminal 53 Low
Voltage
0.07 V*
Parameter 6-11
Terminal 53
High Voltage
10 V*
Parameter 6-14
Terminal 53 Low
Ref./Feedb.
Value
0 RPM
Parameter 6-15
Terminal 53
High Ref./Feedb.
Value
1500 RPM
*=Default value
Notes/comments:
Table 8.3 Wiring Configuration for Analog Speed Reference
(Voltage)
Parameters
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
+
-
FC
e30bb927.11
A53
U - I
4 - 20mA
Function
Setting
Parameter 6-12 T
erminal 53 Low
Current
4 mA*
Parameter 6-13 T
erminal 53 High
Current
20 mA*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
1500 RPM
*=Default value
Notes/comments:
Table 8.4 Wiring Configuration for Analog Speed Reference
(Current)
8.4 Wiring Configurations for Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start*
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
Parameter 5-19 T
erminal 37 Safe
Stop
[1] Safe
Torque Off
Alarm
*=Default value
Notes/comments:
If
parameter 5-12 Terminal 27
Digital Input
is set to
[0] No
operation
, a jumper wire to
terminal 27 is not needed.
Table 8.5 Wiring Configuration for Start/Stop Command with
Safe Torque Off
Wiring Configuration Exampl...
Operating Guide
MG34U502
Danfoss A/S © 09/2018 All rights reserved.
73