e30bf228.11
L1
L2
L3
PE
PE
u
v
w
2
1
3
5
16
17
18
14
12
8
7
10
9
4
11
13
4
6
15
90
4
1
PLC
10
Mains cable (unshielded)
2
Minimum 16 mm
2
(6 AWG) equalizing cable
11
Output contactor and similar options
3
Control cables
12
Cable insulation stripped
4
Required minimum separation of 200 mm (7.9 in) between
control cables, motor cables, and mains cables
13
Common ground busbar (Follow local and national
requirements for enclosure grounding)
5
Mains supply
14
Brake resistor
6
Bare (unpainted) surface
15
Metal box
7
Star washers
16
Connection to motor
8
Brake cable (shielded)
17
Motor
9
Motor cable (shielded)
18
EMC cable gland
Illustration 5.1 Example of Proper EMC Installation
Electrical Installation
Operating Guide
MG34U502
Danfoss A/S © 09/2018 All rights reserved.
25
5
5
Summary of Contents for VLT AutomationDrive FC 302