Floor mounting the drive
To secure the pedestal to the floor (after attaching the
drive to the pedestal), use the following steps.
1.
Fasten 4 M10 bolts in the mounting holes at the
bottom of the pedestal, securing it to the floor.
See
.
2.
Reposition the pedestal front cover plate, and
fasten with 4 M5 screws. See
.
3.
Slide the pedestal wall spacer behind the
mounting flange at the top of the drive. See
4.
Fasten 2–4 M10 bolts in the mounting holes at
the top of the drive, securing it to the wall. Use 1
bolt for each mounting hole. The number varies
with enclosure size. See
1
2
e30bg289.10
1
Mounting holes
2
Bottom of pedestal
Illustration 4.7 Pedestal-to-floor Mounting Holes
Wall mounting the drive
To wall mount a drive, use the following steps. Refer to
1.
Fasten 2 M10 bolts in the wall to align with the
fastener slots at the bottom of drive.
2.
Slide the fastener slots over the M10 bolts.
3.
Tip the drive against the wall, and secure the top
with 2 M10 bolts in the mounting holes.
1
2
e30bg288.10
1
Top mounting holes
2
Lower fastener slots
Illustration 4.8 Drive-to-wall Mounting Holes
Mechanical Installation
VLT® AutomationDrive FC 302
22
Danfoss A/S © 09/2018 All rights reserved.
MG34U502
4
4
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......