11.2 International/North American Default Parameter Settings
Setting
parameter 0-03 Regional Settings
to
[0] International
or
[1] North America
changes the default settings for some
parameters.
lists those parameters that are affected.
Parameter
International default parameter value
North American default parameter value
Parameter 0-03 Regional Settings
International
North America
Parameter 0-71 Date Format
DD-MM-YYYY
MM/DD/YYYY
Parameter 0-72 Time Format
24 h
12 h
Parameter 1-20 Motor Power [kW]
1)
1)
Parameter 1-21 Motor Power [HP]
2)
2)
Parameter 1-22 Motor Voltage
230 V/400 V/575 V
208 V/460 V/575 V
Parameter 1-23 Motor Frequency
50 Hz
60 Hz
Parameter 3-03 Maximum Reference
50 Hz
60 Hz
Parameter 3-04 Reference Function
Sum
External/Preset
Parameter 4-13 Motor Speed High Limit
[RPM]
3)
1500 RPM
1800 RPM
Parameter 4-14 Motor Speed High Limit [Hz]
4)
50 Hz
60 Hz
Parameter 4-19 Max Output Frequency
100 Hz
120 Hz
Parameter 4-53 Warning Speed High
1500 RPM
1800 RPM
Parameter 5-12 Terminal 27 Digital Input
Coast inverse
External interlock
Parameter 5-40 Function Relay
Alarm
No alarm
Parameter 6-15 Terminal 53 High Ref./Feedb.
Value
50
60
Parameter 6-50 Terminal 42 Output
Speed 0-HighLim
Speed 4-20 mA
Parameter 14-20 Reset Mode
Manual reset
Infinite auto reset
Parameter 22-85 Speed at Design Point
[RPM]
3)
1500 RPM
1800 RPM
Parameter 22-86 Speed at Design Point [Hz]
50 Hz
60 Hz
Parameter 24-04 Fire Mode Max Reference
50 Hz
60 Hz
Table 11.2 International/North American Default Parameter Settings
1) Parameter 1-20 Motor Power [kW] is only visible when parameter 0-03 Regional Settings is set to [0] International.
2) Parameter 1-21 Motor Power [HP] is only visible when parameter 0-03 Regional Settings is set to [1] North America.
3) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [0] RPM.
4) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [1] Hz.
11.3 Parameter Menu Structure