Type aR fuses are recommended for drives in enclosure sizes D3h–D4h. See
.
Model
200–240 V
380–500 V
525–690 V
N45K
ar-350
–
–
N55K
ar-400
–
ar-160
N75K
ar-500
–
ar-315
N90K
ar-500
ar-315
ar-315
N110
ar-630
ar-350
ar-315
N132
–
ar-400
ar-315
N150
ar-800
–
–
N160
–
ar-500
ar-550
N200
–
ar-630
ar-550
N250
–
ar-800
ar-550
N315
–
–
ar-550
Table 10.10 D3h–D4h Power/Semiconductor Fuse Sizes
Bussmann
Rating
LPJ-21/2SP
2.5 A, 600 V
Table 10.11 D1h–D8h Space Heater Fuse Recommendation
For UL compliance, use the Bussmann 170M series fuses for units supplied without a disconnect, contactor, or circuit breaker
option. If a disconnect, contactor, or circuit breaker option is supplied with the drive, see
to
for SCCR
ratings and UL fuse criteria.
10.7.2 Short-circuit Current Rating (SCCR)
The short-circuit current rating (SCCR) represents the maximum level of short-circuit current that the drive can safely
withstand. If the drive is not supplied with a mains disconnect, contactor, or circuit breaker, the SCCR of the drive is 100000
A at all voltages (200–690 V).
If the drive is supplied with a mains disconnect only, the SCCR of the drive is 100000 amps at all voltages (200–600 V). See
. If the drive is supplied with a contactor only, refer to
for the SCCR. If the drive contains both a
contactor and disconnect, see
If the drive is supplied with a circuit breaker only, the SCCR depends on the voltage. Refer to
Enclosure size
≤ 600 V IEC/UL
D5h
100000 A
1)
D7h
100000 A
2)
Table 10.12 D5h and D7h Drives Supplied with a Disconnect Only
1)
With an upstream branch protection Class J fuse with maximum rating of 600 A.
2)
With an upstream branch protection Class J fuse with maximum rating of 800 A.
Enclosure size
415 V
IEC
1)
480 V
UL
2)
600 V
UL
2)
690 V
IEC
1)
D6h
100000 A
100000 A
100000 A
100000 A
D8h (excluding N250 380-500V model)
100000 A
100000 A
100000 A
100000 A
D8h (N250 380-500V model only)
100000 A
Contact Danfoss
Not applicable
Not applicable
Table 10.13 D6h and D8h Drives Supplied with a Contactor Only
1)
With gL/gG fuses: 425 A maximum fuse size for D6h, and 630 A maximum fuse size for D8h.
2)
With external upstream Class J fuses: 450 A maximum fuse size for D6h, and 600 A maximum fuse size for D8h.
Specifications
Operating Guide
MG34U502
Danfoss A/S © 09/2018 All rights reserved.
107
10
10