FC 202, P45KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
480
0.368
1.270
2.853
50
480
0.536
1.260
1.978
100
480
0.680
1.240
1.426
150
480
0.712
1.200
1.334
FC 202, P55KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
15
480
0.256
1.230
3.847
50
480
0.328
1.200
2.957
100
480
0.456
1.200
2.127
150
480
0.960
1.150
1.052
FC 202, P75KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
FC 202, P90KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
480
0.371
1.170
2.523
High Power Range:
FC 202, P110 - P250, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
400
0.34
1.040
2.447
FC 202, P315 - P1M0, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
500
0.71
1.165
1.389
30
400
0.61
0.942
1.233
FC 202, P110 - P400, T7
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
690
0.38
1.513
3.304
30
575
0.23
1.313
2.750
30
690
1)
1.72
1.329
0.640
1) With Danfoss dU/dt filter.
3 VLT AQUA Selection
VLT
®
AQUA Drive Design Guide
58
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
3