NB!
The gland plate must be fitted to the frequency converter to ensure the specified protection degree, as well as ensuring proper cooling
of the unit. If the gland plate is not mounted, the frequency converter may trip on Alarm 69, Pwr. Card Temp
Illustration 5.11: Example of proper installation of the gland plate.
Frame size D1 + D2
Frame size E1
Cable entries viewed from the bottom of the frequency converter - 1) Mains side 2) Motor side
5 How to Install
VLT
®
AQUA Drive Design Guide
118
MG.20.N5.02 - VLT
®