VLT AQUA
Bussmann
Bussmann
Bussmann
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
380-500 V, 525-600
kW
Type RK1
Type J
Type T
Type RK1
Type RK1
Type CC
Type RK1
11K
KTS-R40
JKS-40
JJS-40
5014006-040
KLS-R40
-
A6K-40R
15K
KTS-R40
JKS-40
JJS-40
5014006-040
KLS-R40
-
A6K-40R
18K
KTS-R50
JKS-50
JJS-50
5014006-050
KLS-R50
-
A6K-50R
22K
KTS-R60
JKS-60
JJS-60
5014006-063
KLS-R60
-
A6K-60R
30K
KTS-R80
JKS-80
JJS-80
2028220-100
KLS-R80
-
A6K-80R
37K
KTS-R100
JKS-100
JJS-100
2028220-125
KLS-R100
A6K-100R
45K
KTS-R125
JKS-150
JJS-150
2028220-125
KLS-R125
A6K-125R
55K
KTS-R150
JKS-150
JJS-150
2028220-160
KLS-R150
A6K-150R
75K
FWH-220
-
-
2028220-200
L50S-225
A50-P225
90K
FWH-250
-
-
2028220-250
L50S-250
A50-P250
Table 5.8: UL fuses 380 - 600 V
KTS-fuses from Bussmann may substitute KTN for 240 V frequency converters.
FWH-fuses from Bussmann may substitute FWX for 240 V frequency converters.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V frequency converters.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V frequency converters.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V frequency converters.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V frequency converters.
Frequency
converter
Bussmann
Bussmann
Bussmann
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
UL Compliance
- 200-240 V
kW
Type RK1
Type J
Type T
Type RK1
Type RK1
Type CC
Type RK1
K25-K37
KTN-R05
JKS-05
JJN-05
5017906-005
KLN-R005
ATM-R05
A2K-05R
K55-1K1
KTN-R10
JKS-10
JJN-10
5017906-010
KLN-R10
ATM-R10
A2K-10R
1K5
KTN-R15
JKS-15
JJN-15
5017906-015
KLN-R15
ATM-R15
A2K-15R
2K2
KTN-R20
JKS-20
JJN-20
5012406-020
KLN-R20
ATM-R20
A2K-20R
3K0
KTN-R25
JKS-25
JJN-25
5012406-025
KLN-R25
ATM-R25
A2K-25R
3K7
KTN-R30
JKS-30
JJN-30
5012406-030
KLN-R30
ATM-R30
A2K-30R
5K5
KTN-R50
JKS-50
JJN-50
5012406-050
KLN-R50
-
A2K-50R
7K5
KTN-R50
JKS-60
JJN-60
5012406-050
KLN-R60
-
A2K-50R
11K
KTN-R60
JKS-60
JJN-60
5014006-063
KLN-R60
A2K-60R
A2K-60R
15K
KTN-R80
JKS-80
JJN-80
5014006-080
KLN-R80
A2K-80R
A2K-80R
18K5
KTN-R125
JKS-150
JJN-125
2028220-125
KLN-R125
A2K-125R
A2K-125R
22K
KTN-R125
JKS-150
JJN-125
2028220-125
KLN-R125
A2K-125R
A2K-125R
30K
FWX-150
-
-
2028220-150
L25S-150
A25X-150
A25X-150
37K
FWX-200
-
-
2028220-200
L25S-200
A25X-200
A25X-200
45K
FWX-250
-
-
2028220-250
L25S-250
A25X-250
A25X-250
Table 5.9:
UL fuses 200 - 240 V
Frequency
converter
Bussmann
Bussmann
Bussmann
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
UL Compliance - 380-480 V, 525-600
kW
Type RK1
Type J
Type T
Type RK1
Type RK1
Type CC
Type RK1
K37-1K1
KTS-R6
JKS-6
JJS-6
5017906-006
KLS-R6
ATM-R6
A6K-6R
1K5-2K2
KTS-R10
JKS-10
JJS-10
5017906-010
KLS-R10
ATM-R10
A6K-10R
3K0
KTS-R15
JKS-15
JJS-15
5017906-016
KLS-R16
ATM-R16
A6K-16R
4K0
KTS-R20
JKS-20
JJS-20
5017906-020
KLS-R20
ATM-R20
A6K-20R
5K5
KTS-R25
JKS-25
JJS-25
5017906-025
KLS-R25
ATM-R25
A6K-25R
7K5
KTS-R30
JKS-30
JJS-30
5012406-032
KLS-R30
ATM-R30
A6K-30R
11K
KTS-R40
JKS-40
JJS-40
5014006-040
KLS-R40
-
A6K-40R
15K
KTS-R40
JKS-40
JJS-40
5014006-040
KLS-R40
-
A6K-40R
18K
KTS-R50
JKS-50
JJS-50
5014006-050
KLS-R50
-
A6K-50R
22K
KTS-R60
JKS-60
JJS-60
5014006-063
KLS-R60
-
A6K-60R
30K
KTS-R80
JKS-80
JJS-80
2028220-100
KLS-R80
-
A6K-80R
37K
KTS-R100
JKS-100
JJS-100
2028220-125
KLS-R100
A6K-100R
45K
KTS-R125
JKS-150
JJS-150
2028220-125
KLS-R125
A6K-125R
55K
KTS-R150
JKS-150
JJS-150
2028220-160
KLS-R150
A6K-150R
75K
FWH-220
-
-
2028220-200
L50S-225
A50-P225
90K
FWH-250
-
-
2028220-250
L50S-250
A50-P250
Table 5.10:
UL fuses 380 - 600 V
KTS-fuses from Bussmann may substitute KTN for 240 V frequency converters.
FWH-fuses from Bussmann may substitute FWX for 240 V frequency converters.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V frequency converters.
VLT
®
AQUA Drive Design Guide
5 How to Install
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
127