Table 48: Electrical Data, Mains Supply 3x525–690 V AC
FC 202
N630
N710
N800
High/normal overloadHigh overload=150% or 160% torque
for a duration of 60 s. Normal overload=110% torque for a du-
ration of 60 s.
HO
NO
HO
NO
HO
NO
Typical shaft output at 525 V [kW]
450
500
500
560
560
670
Typical shaft output at 575 V [hp]
600
650
650
750
750
950
Typical shaft output at 690 V [kW]
560
630
630
710
710
800
Enclosure size
E1h/E3h
E2h/E4h
E2h/E4h
Output current (3-phase)
Continuous (at 525 V) [A]
596
630
659
763
763
889
Intermittent (60 s overload) (at 525 V) [A]
894
693
989
839
1145
978
Continuous (at 575/690 V) [A]
570
630
630
730
730
850
Intermittent (60 s overload) (at 575/690 V) [A]
855
693
945
803
1095
935
Continuous kVA (at 525 V) [kVA]
542
573
599
694
694
808
Continuous kVA (at 575 V) [kVA]
568
627
627
727
727
847
Continuous kVA (at 690 V) [kVA]
681
753
753
872
872
1016
Maximum input current
Continuous (at 525 V) [A]
574
607
635
735
735
857
Continuous (at 575/690 V) [A]
549
607
607
704
704
819
Maximum number and size of cables per phase (E1h/E2h)
- Mains and motor without brake [mm
2
(AWG)]
5x240 (5x500 mcm)
6x240 (5x500 mcm)
6x240 (5x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
4x240 (4x500 mcm)
5x240 (4x500 mcm)
5x240 (4x500 mcm)
- Brake or regen [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E3h/E4h)
- Mains and motor [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regen [mm
2
(AWG)]
4x185 (4x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
(1)
800
1200
1200
Estimated power loss at 600 V [W]
(2) (3)
7624
8676
8054
9709
9661
11848
Estimated power loss at 690 V [W]
(2) (3)
7842
8915
8357
10059
10010
12253
Efficiency
(3)
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
80 (176)
Power card overtemperature trip [°C (°F)]
85 (185)
85 (185)
85 (185)
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
134 | Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...