Parameter settings
Table 36: Relevant Parameters for Submersible Pump Application
Parameter
Parameter 1-20 Motor Power [kW]/parameter 1-21 Motor Power [HP]
Parameter 1-22 Motor Voltage
Parameter 1-24 Motor Current
Parameter 1-28 Motor Rotation Check
Parameter 1-29 Automatic Motor Adaptation (AMA)
=
[2] Enable Reduced AMA
Table 37: Example of Settings for Submersible Pump
Parameter
Setting
Parameter 3-02 Minimum Reference
The minimum reference unit matches the unit in
parameter 20-12 Reference/ Feed-
back Unit
Parameter 3-03 Maximum Reference
The maximum reference unit matches the unit in
parameter 20-12 Reference/ Feed-
back Unit
Parameter 3-84 Initial Ramp Time
(2 s)
Parameter 3-88 Final Ramp Time
(2 s)
Parameter 3-41 Ramp 1 Ramp Up Time
(8 s depending on size)
Parameter 3-42 Ramp 1 Ramp Down Time
(8 s depending on size)
Parameter 4-11 Motor Speed Low Limit [RPM]
(30 Hz)
Parameter 4-13 Motor Speed High Limit [RPM]
(50/60 Hz)
To set up the feedback settings in the PID controller, use the Closed-loop wizard under Quick Menu, Function Set-up.
Table 38: Example of Settings for Pipe-Fill Mode
Parameter
Setting
Parameter 29-00 Pipe Fill Enable
Disabled
Parameter 29-04 Pipe Fill Rate
(Feedback units)
Parameter 29-05 Filled Setpoint
(Feedback units)
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 93
Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...