9 Specifications
9.1 Electrical Data
9.1.1 Electrical Data, 380–480 V AC
Table 45: Electrical Data, Mains Supply 3x380–480 V AC
FC 202
N355
N400
N450
High/normal overload
High overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
315
355
355
400
400
450
Typical shaft output at 460 V [hp]
450
500
500
550
550
600
Typical shaft output at 500 V [kW]
355
400
400
500
500
530
Enclosure size
E1h/E3h
E1h/E3h
E1h/E3h
Output current (3-phase)
Continuous (at 400 V) [A]
600
658
658
745
695
800
Intermittent (60 s overload) (at 400 V) [A]
900
724
987
820
1043
880
Continuous (at 460/480 V) [A]
540
590
590
678
678
730
Intermittent (60 s overload) (at 460/480 V) [A]
810
649
885
746
1017
803
Continuous kVA (at 400 V) [kVA]
416
456
456
516
482
554
Continuous kVA (at 460 V) [kVA]
430
470
470
540
540
582
Continuous kVA (at 480 V) [kVA]
449
491
491
564
564
607
Maximum input current
Continuous (at 400 V) [A]
578
634
634
718
670
771
Continuous (at 460/480 V) [A]
520
569
569
653
653
704
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
2
(AWG)]
5x240 (5x500 mcm)
5x240 (5x500 mcm)
5x240 (5x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
- Brake or regen [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regen [mm
2
(AWG)]
4x185 (4x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
(1)
800
800
800
Estimated power loss at 400 V [W]
(2) (3)
6178
6928
6851
8036
7297
8783
Estimated power loss at 460 V [W]
(2) (3)
5322
5910
5846
6933
7240
7969
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
130 | Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...