7 Plastic cable entry plate (installed)
9 Keyhole opening
8 Fastener point
Illustration 15: Assembling the Cable Entry Plate and Terminal Cover
4.10.3 Installing Load share/Regen Terminals to an E3h/E4h
Context:
The load share/regen terminals, on the top of the drive, are not installed from the factory to prevent damage during shipping.
Procedure
1. Remove the terminal plate, 2 terminals, label, and fasteners from the accessory bag included with the drive.
2. Remove the cover from the load share/ regen opening on the top of the drive. Put aside the 2 M5 fasteners for reuse later.
3. Remove the plastic backing and install the terminal plate over the load share/regen opening. Secure with the 2 M5 fasteners and
torque to 2.3 Nm (20 in-lb).
4. Install both the terminals to the terminal plate using 1 M10 fastener per terminal. Torque to 19 Nm (169 in-lb).
5. Install the label on the front of the terminals as shown in
. Secure with 2 M4 screws and torque to 1.2 Nm (10 in-lb).
Example:
e
3
0
b
f6
9
7
.1
0
3
5
4
1
2
1 Label fastener, M4
3 Load share/regen terminal
5 Terminal plate with 2 openings
2 Label
4 Terminal fastener, M10
Illustration 16: Load share/Regen Terminals
Mechanical Installation
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
34 | Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...