7.1.6 Wiring Configuration: Start/Stop
Table 28: Start/Stop Command with Safe Torque Off Option
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
12
13
18
19
20
27
29
32
33
37
e3
0b
b8
02
.1
2
Drive
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[Start]*
Parameter 5-12 Terminal 27 Digital Input
[0] No operation
Parameter 5-19 Terminal 37 Safe Stop
[1] Safe Stop Alarm
*=Default value
Notes/comments:
If
parameter 5-12 Terminal 27 Digital Input
is set
[0] No operation
, a jumper wire to terminal 27 is
not needed.
D IN 37 is an option.
e3
0b
b8
05
.1
3
Speed
Start/Stop (18)
Illustration 41: Start/Stop Command with Safe Torque Off
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
84 | Danfoss A/S © 2020.01