FC 202
N355
N400
N450
Efficiency
(3)
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
80 (176)
Power card overtemperature trip [°C (°F)]
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip [°C (°F)]
85 (185)
85 (185)
85 (185)
Active in-rush card overtemperature trip [°C (°F)]
85 (185)
85 (185)
85 (185)
1
.
2
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3
. For part load losses, see www.danfoss.com/vltenergyefficiency.
Table 46: Electrical Data, Mains Supply 3x380–480 V AC
FC 202
N500
N560
High/normal overloadHigh overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
450
500
500
560
Typical shaft output at 460 V [hp]
600
650
650
750
Typical shaft output at 480 V [kW]
530
560
560
630
Enclosure size
E2h/E4h
E2h/E4h
Output current (3-phase)
Continuous (at 400 V) [A]
800
880
880
990
Intermittent (60 s overload) (at 400 V) [A]
1200
968
1320
1089
Continuous (at 460/480 V) [A]
730
780
780
890
Intermittent (60 s overload) (at 460/480 V) [A]
1095
858
1170
979
Continuous kVA (at 400 V) [kVA]
554
610
610
686
Continuous kVA (at 460 V) [kVA]
582
621
621
709
Continuous kVA (at 480 V) [kVA]
607
648
648
740
Maximum input current
Continuous (at 400 V) [A]
771
848
848
954
Continuous (at 460/480 V) [A]
704
752
752
858
Maximum number and size of cables per phase (E2h)
- Mains and motor without brake [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
5x240 (4x500 mcm)
5x240 (4x500 mcm)
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 131
Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...