7.1.2 Wiring Configuration for Automatic Motor Adaptation without T27
Table 17: AMA without T27 Connected
Parameters
Drive
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
e3
0b
b9
30
.1
1
Function
Setting
Parameter 1-29 Automatic Motor Adaptation (AMA)
[1] Enable complete
AMA
Parameter 5-12 Terminal 27 Digital Input
[0] No operation
*=Default value
Notes/comments:
Parameter group 1-2* Motor Data
must be set ac-
cording to motor.
7.1.3 Wiring Configuration: Speed
Table 18: Analog Speed Reference (Voltage)
Parameters
+10 V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
0–10 V
+
-
e
3
0
b
b
9
2
6
.1
1
Drive
Function
Setting
Parameter 6-10 Terminal 53 Low Voltage
0.07 V*
Parameter 6-11 Terminal 53 High Voltage
10 V*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708| 75
Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...