300-52 Sleep Mode Wake Up Trigger
Range:
Function:
Application
dependent
*
[Application
dependant]
Only available when
[o] Line
Power Current
is selected in
.
The parameter sets the current
% value of
at which the filter awakes;
5 equals 5% of
. If CTs are 1500 and this
parameter is 5, this equals 5% of
1500A = 75A wake-up current.
300-53 Sleep Mode Sleep Trigger
Range:
Function:
80 %
*
[0 - 90 %]
6.10 301-**
301-00 Output Current [A]
Range:
Function:
0.00 A
*
[0.00 - 10000.00 A] View the RMS output current of
the unit.
301-01 Output Current [%]
Range:
Function:
0.0 %
*
[0.0 - 10000.0 %]
301-10 THD of Current [%]
Range:
Function:
0 %
*
[0 - 200 %]
301-11 Estimated THD of Voltage [%]
Range:
Function:
0%
*
[0–200%] View the total harmonic distortion of the
voltage. This value is estimated because the
active filter does not measure the AC line
voltage.
301-12 Power Factor
Range:
Function:
0.00
*
[0.00 - 2.00 ] View the power factor, after compensation
by the active filter.
301-13 Cosphi
Range:
Function:
0.00
*
[-1.00 -
2.00 ]
View the displacement power factor, after
compensation by the active filter. Positive
numbers indicate a leading power factor,
while negative numbers indicate a lagging
power factor.
301-14 Leftover Currents
Range:
Function:
0.0 A
*
[0.0 - 8000.0 A] View the harmonic currents leftover
after prioritized harmonic and cos-phi
compensation by the active filter.
301-20 Mains Current [A]
Range:
Function:
0 A
*
[0 - 65000 A] View the total harmonic distortion of the
current, after compensation by the active
filter.
301-21 Mains Frequency
Range:
Function:
0 Hz
*
[0 - 100 Hz] View the total harmonic distortion of the
voltage.
301-22 Fund. Mains Current [A]
Range:
Function:
0 A
*
[0 - 65000 A] View the power factor, after compensation
by the active filter.
How to Program
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6-27
6
6