6.8 16-0* General Status
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the control word sent from the unit via
the serial communication port in hex code.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the status word sent from the unit via the
serial communication port in hex code.
16-30 DC Link Voltage
Range:
Function:
0 V
*
[0 - 10000 V] View a measured value. The value is filtered
with an 30ms time constant.
16-34 Heatsink Temp.
Range:
Function:
0 C
*
[0 - 255 C]
16-35 Inverter Thermal
Range:
Function:
0 %
*
[0 - 100 %] View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range:
Function:
Application
dependent
*
[0.01 - 10000.00 A] View the inverter
nominal current.
16-37 Inv. Max. Current
Range:
Function:
Application
dependent
*
[0.01 - 10000.00 A] View the inverter
maximum current.
16-39 Control Card Temp.
Range:
Function:
0 C
*
[0 - 100 C]
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group 15-1*). The logging buffer will never be full
when
is set to
Log always
[0].
[0]
*
No
[1]
Yes
16-49 Current Fault Source
Range:
Function:
0
*
[0 - 8 ] Value indicates source of current faults including
short circuit, overcurrent, and phase imbalance
(from left):
16-49 Current Fault Source
Range:
Function:
1-4 Inverter
5-8 Rectifier
0 No fault recorded
6.8.1 16-6* Inputs & Outputs
16-60 Digital Input
Range:
Function:
0
*
[0 -
1023 ]
View the signal states from the active digital inputs.
Example: Input 18 corresponds to bit no. 5, ‘0’ = no
signal, ‘1’ = connected signal. Bit 6 works in the
opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
D I T - 3 3
D I T - 3 2
D I T - 2 9
D I T - 2 7
D I T - 1 9
D I T - 1 8
D I T - 3 7
D I X 3 0/4
D I X 3 0/3
D I X 3 0/2
D I X 4 6/ 1 3
D I X 4 6/ 1 1
D I X 4 6/9
D I X 4 6/ 7
D I X 4 6/ 5
D I X 4 6/3
D I X 4 6/ 1
130BA894.10
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
16-66 Digital Output [bin]
Range:
Function:
0
*
[0 - 15 ]
View the binary value of all digital outputs.
How to Program
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6-23
6
6