4.5.14 Control Wire Installation
All terminals to the control cables are located on the AFC
board.
To connect the cable to the terminal:
1.
Strip insulation by about 0.34–0.39 in [9–10 mm].
130BA150.10
9 - 10 mm
(0.37 in)
2.
Insert a screwdriver
1)
in the square hole.
130B
T312.10
3.
Insert the cable in the adjacent circular hole.
130B
T311.10
4.
Remove the screwdriver. The cable is now
mounted in the terminal.
To remove the cable from the terminal:
1.
Insert a screw driver
1)
in the square hole.
2.
Pull out the cable.
1) Max. 0.015 x 0.1 in [0.4 x 2.5 mm]
Remove jumper to activate Safe Stop
Max. 24
Volt !
12 13
12
19 27
29
32
33 20
39 42
50
53 54
61 68
130BB744.10
4.5.15 Unshielded Control Wires
CAUTION
Induced Voltage!
Run input power and control wiring in separate metallic
conduits or raceways for high frequency noise isolation.
Failure to isolate power and control wiring could result in
less than optimum controller and associated equipment
performance.
Control wiring including CT wires should always be
isolated from the high voltage power wiring. When
shielded/armored cable is not used, ensure that control
wires are twisted pairs and keep the maximum possible
distance between line power wire and control cables.
4.5.16 External Fan Supply
If the active filter is supplied by DC or if the fan must run
independently of the power supply, an external power
supply can be applied.
Terminal No.
Function
100, 101
102, 103
Auxiliary supply S, T
Internal supply S, T
How to Install
VLT Active Filter AAF 00x
4-30
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark