8-35 Minimum Response Delay
Range:
Function:
10 ms
*
[Application
dependant]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is used
for overcoming modem turnaround
delays.
8-36 Max Response Delay
Range:
Function:
Application
dependent
*
[Application
dependant]
Specify the maximum
permissible delay time
between transmitting a
request and receiving a
response. Exceeding this delay
time will cause control word
timeout.
8-37 Max Inter-Char Delay
Range:
Function:
Application
dependent
*
[Application
dependant]
Specify the maximum
permissible time interval
between receiving two bytes.
This parameter activates
timeout if transmission is
interrupted.
This parameter is active only
when
is set to
FC
MC
[1] protocol.
8-53 Start Select
Option:
Function:
Select control of the unit start function via the
terminals (digital input) and/or via the Serial
communication bus.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or Serial communication
bus option.
[2]
Logic
AND
Activates Start command via the Serial
communication bus/serial communication port,
AND additionally via one of the digital inputs.
[3]
*
Logic OR
Activates Start command via the Serial
communication bus/serial communication port
OR via one of the digital inputs.
NOTE!
This parameter is active only when
is set
to [0] Digital and control word.
8-55 Set-up Select
Option:
Function:
Select control of the unit set-up selection via
the terminals (digital input) and/or via the Serial
communication bus.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port or Serial communication
bus option.
[2]
Logic
AND
Activates the set-up selection via the Serial
communication bus/serial communication port,
AND additionally via one of the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the Serial
communication bus/serial communication port
OR via one of the digital inputs.
NOTE!
This parameter is active only when
is set
to [0] Digital and control word.