MK108
1A CT connection pin
MK102
I/O connections
MK101
5A CT connection pin
91-93
Line power input
MK103
Software communication RS-485
NOTE!
Terminals are not all located on the same PCB.
In rare cases, very long control cables and analog signals
may, depending on installation, result in 50/60 Hz ground
loops due to noise from line power supply cables.
If this occurs, it may be necessary to break the shield or
insert a 100 nF capacitor between shield and chassis.
Input polarity of control terminals
12
13
18
19
27
29
32
33
20
37
+24
V DC
0
VDC
130
BT106.10
PNP (Source)
Digital input wiring
NPN (Sink)
Digital input wiring
12
13
18
19
27
29
32
33
20
37
+24
V DC
0
VDC
130
BT107.11
NOTE!
To comply with EMC emission specifications, shielded
cables are recommended. If a non-shielded cable is used,
see
4.5.15 Unshielded Control Wires
. If non-shielded control
cables are used, it is recommended to use ferrite cores to
improve EMC performance.
130BB745.10
61 68
39 42
50 53
54
Remov
e jumper to ac
tivate Safe Stop
Max. 24
Volt !
12 13
12 19
27 29
32 33
20
Remember to connect the shields in a proper way to
ensure optimum electrical immunity.
How to Install
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
4-33
4