5-10 Terminal 18 Digital Input
Option:
Function:
[100] Follower AF
#2 Run
Feedback
Do not program this setting. It is done
automatically for paralleling. See
parameter 300-40 Master Follower Selection
and
parameter 300-41 Follower ID
for more
information about paralleling.
[101] Sleep
The filter goes into sleep mode at light duty
to save energy.
5-11 Terminal 19 Digital Input
Option:
Function:
[0]
*
No Operation Functions are described under
5-1* Digital
Inputs
5-12 Terminal 27 Digital Input
Option:
Function:
[0]
*
No Operation Functions are described under
5-1* Digital
Inputs
5-13 Terminal 29 Digital Input
Option:
Function:
[0]
*
No Operation Functions are described under
5-1* Digital
Inputs
5-16 Terminal X30/2 Digital Input
Option:
Function:
[0]
*
No operation Functions are described under
5-1* Digital
Inputs
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0]
*
No operation Functions are described under
5-1* Digital
Inputs
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0]
*
No operation Functions are described under
5-1* Digital
Inputs
5-19 Terminal 37 Safe Torque Off (STO)
Function
Number
PTC
Relay
No Function
[0]
-
-
Safe Torque Off
(STO) Alarm
[1]*
-
safe torque off
[A68]
Table 6.9 Overview of Functions, Alarms and Warnings
6.5.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
parameter 5-01 Terminal 27 Mode
, and set
the I/O function for terminal 29 in
parameter 5-02 Terminal
29 Mode
. These parameters cannot be adjusted while the
unit is running.
5-30 Terminal 27 Digital Output
Option:
Function:
[0]
No operation
Default for all digital outputs and relay
outputs.
[1]
Control ready
The control card is ready. E.g.: Feedback
from a unit where the control is supplied
by an external 24 V (MCB 107) and the
main power to the unit is not detected.
[2]
Unit ready
The unit is ready for operation and applies
a supply signal on the control board.
[4]
Enable / no
warning
Ready for operation. No start or stop
command is been given (start/disable). No
warnings are active.
[5]
Running
The motor is running and shaft torque
present.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[12]
Current limit
The motor current is outside the range set
in
4-18 Current Limit
. The active filter
current is at the limit.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
active filter.
[22]
Ready,no
thermal W
The unit is ready for operation and there
is no overtemperature warning.
[24]
Ready, voltage
OK
The unit is ready for operation and the
mains voltage is within the specified
voltage range.
[26]
Bus OK
Active communication (no time-out) via
the serial communication port.
[55]
Pulse output
[122] No alarm
[125] Hand mode
Output is high when the unit is in
Hand
on
mode (as indicated by the LED light
above [Hand on]).
[126] Auto mode
[152] AF sleeping
5-31 Terminal 29 Digital Output
Option:
Function:
[0]
*
No operation Functions are described under parameter
group
5-3* Digital Outputs
Applications and Basic Prog...
Operating Instructions
MG90V302
Danfoss A/S © 09/2014 All rights reserved.
47