01 My Personal Menu
02 Quick Setup
05 Changes Made
06 Loggings
0.0% 0.00
Quick Menus
1(1)
130BB473.10
Illustration 6.5 Quick Menu View
If
No Operation
is selected in terminal 27, no connection to
+24 V on terminal 27 is necessary to enable start.
If
Coast Inverse
is selected in Terminal 27, a connection to
+24 V is necessary to enable start.
6.2.2 Q1 My Personal Menu
Parameters defined by the user can be stored in
Q1 My
Personal Menu
. Select
My Personal Menu
to display only the
parameters, which have been pre-selected and
programmed as personal parameters. A large-scale active
filter user may have pre-programmed important set-up
values in the
My Personal Menu
to make on-site commis-
sioning/fine-tuning simpler. These parameters are selected
in
parameter 0-25 My Personal Menu
. Up to 20 different
parameters can be defined in this menu.
Q1 My Personal Menu
Parameter number and Name
Factory default
0-01 Language
English
0-20 Display Line 1.1 Small
Power Factor
0-21 Display Line 1.2 Small
THD of current
0-22 Display Line 1.3 Small
Mains current
0-23 Display Line 2 Large
Output current (corrected)
0-24 Display Line 3 Large
Mains frequency
15-51 Frequency Converter Serial
Number
Table 6.2 My Personal Menu Settings
6.2.3 Q2 Quick Setup
The parameters in
Q2 Quick Setup
are the basic parameters
that are always needed to set up the active filter.
Q2 Quick Setup
Parameter number and
Name
Factory default
0-01 Language
English
300-22 CT Nominal Voltage
Same as AF
Parameter 300-29 Start Auto
CT Detection
Off
Parameter 300-01 Compen-
sation Priority
Harmonics
Parameter 300-00 Harmonic
Cancellation Mode
Overall
Table 6.3 Quick Setup Settings
NOTICE
Set the nominal voltage and CT secondary rating and
change
parameter 300-26 CT Placement
to PCC before
starting the Auto CT detection. Auto CT detection is only
possible if CTs are located at the point of common
coupling.
6.2.4 Q5 Changes Made
Use
Q5 Changes Made
for fault finding.
Select
Q5 Changes Made
to get information about:
•
The 10 most recent changes. Use
▲
and
▼
to
scroll between the last 10 parameters changed.
•
Changes made since default setting.
6.2.5 Q6 Loggings
Use
Q6 Loggings
for fault finding.
Select
Loggings
to get information about the display line
readouts. The information is shown as graphs. Only display
parameters selected in
0-20 Display Line 1.1 Small
and
0-24 Display Line 3 Large
can be viewed. It is possible to
store up to 120 samples in the memory for later reference.
Note that the parameters listed in
Table 6.4
for Q6 only
serve as examples as they vary depending on the
programming of the particular active filter.
Q6 Loggings
0-20 Display Line 1.1 Small
Power Factor
0-21 Display Line 1.2 Small
THD of current
0-22 Display Line 1.3 Small
Mains Current
0-23 Display Line 2 Large
Output Current
0-24 Display Line 3 Large
Mains Frequency
Table 6.4 Loggings Parameter Examples
Applications and Basic Prog...
Operating Instructions
MG90V302