6.9 16-** Data Readouts
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the control word sent from the unit via
the serial communication port in hex code.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the status word sent from the unit via the
serial communication port in hex code.
16-30 DC Link Voltage
Range:
Function:
0 V
*
[0 - 10000 V] View a measured value. The value is filtered
with a 30 ms time constant.
16-34 Heatsink Temp.
Range:
Function:
0 °C
*
[0 - 255
°C]
View the heat sink temperature. The cut-out
limit is 90 ± 5
°
C, and the filter cuts back in
at 60 ± 5
°
C.
16-35 Inverter Thermal
Range:
Function:
0 %
*
[0 - 100 %] View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range:
Function:
Size related
*
[0.01 - 10000 A] View the inverter nominal
current.
16-37 Inv. Max. Current
Range:
Function:
Size related
*
[0.01 - 10000 A] View the inverter maximum
current.
16-39 Control Card Temp.
Range:
Function:
0 °C
*
[0 - 100 °C] View the temperature on the control card,
stated in
°
C
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group
15-1* Data Log Settings
). The logging buffer is
never full when setting
parameter 15-13 Logging Mode
to
[0] Log always
.
[0]
*
No
[1]
Yes
16-49 Current Fault Source
Range:
Function:
0
*
[0 - 8] Value indicates source of current faults including
short circuit, overcurrent, and phase imbalance
(from left):
1-4 Inverter
5-8 Rectifier
0 No fault recorded
6.9.1 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[0 -
1023 ]
View the signal states from the active digital inputs.
Example: Input 18 corresponds to bit no. 5, 0=no
signal, 1=connected signal. Bit 6 works in the
opposite way, on=0, off=1 (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
Table 6.10 Active Digital Inputs
Illustration 6.9 Relay Settings
16-66 Digital Output [bin]
Range:
Function:
0
*
[0 - 15]
View the binary value of all digital outputs.
Applications and Basic Prog...