6.12.3 5-** Digital In/Out
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
5-0* Digital I/O mode
5-00
Digital I/O mode
[0] PNP
All set-ups
FALSE
-
Uint8
5-01
Terminal 27 mode
[0] Input
All set-ups
TRUE
-
Uint8
5-02
Terminal 29 mode
[0] Input
All set-ups
TRUE
-
Uint8
5-1* Digital Inputs
5-10
Terminal 18 digital input
[8] Start
All set-ups
TRUE
-
Uint8
5-11
Terminal 19 digital input
[0] No operation
All set-ups
TRUE
-
Uint8
5-12
Terminal 27 digital input
[0] No operation
All set-ups
TRUE
-
Uint8
5-13
Terminal 29 digital input
[0] No operation
All set-ups
TRUE
-
Uint8
5-16
Terminal X30/2 digital input
[0] No operation
All set-ups
TRUE
-
Uint8
5-17
Terminal X30/3 digital input
[0] No operation
All set-ups
TRUE
-
Uint8
5-18
Terminal X30/4 digital input
[0] No operation
All set-ups
TRUE
-
Uint8
5-19
Terminal 37 Safe stop
[1] Safe Stop Alarm
1 set-up
TRUE
-
Uint8
5-3* Digital Outputs
5-30
Terminal 27 Digital output
[0] No operation
All set-ups
TRUE
-
Uint8
5-31
Terminal 29 Digital output
[0] No operation
All set-ups
TRUE
-
Uint8
5-4* Relays
5-40
Function relay
[0] No operation
All set-ups
TRUE
-
Uint8
5-41
On delay, relay
0.30 s
All set-ups
TRUE
-2
Uint16
5-42
Off delay, relay
0.30 s
All set-ups
TRUE
-2
Uint16
6.12.4 8-** Comm. and Options
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
8-0* General Settings
8-01
Control site
[0] Digital and ctrl.word
All set-ups
TRUE
-
Uint8
8-02
Control word source
null
All set-ups
TRUE
-
Uint8
8-03
Control word timeout time
1.0 s
1 set-up
TRUE
-1
Uint32
8-04
Control word timeout function
[0] Off
1 set-up
TRUE
-
Uint8
8-05
End-of-timeout Function
[1] Resume set-up
1 set-up
TRUE
-
Uint8
8-06
Reset control word timeout
[0] Do not reset
All set-ups
TRUE
-
Uint8
8-3* FC Port Settings
8-30
Protocol
[1] FC MC
1 set-up
TRUE
-
Uint8
8-31
Address
2 N/A
1 set-up
TRUE
0
Uint8
8-32
FC port baud rate
[2] 9600 Baud
1 set-up
TRUE
-
Uint8
8-35
Minimum response delay
10 ms
All set-ups
TRUE
-3
Uint16
8-36
Max response delay
5000 ms
1 set-up
TRUE
-3
Uint16
8-37
Max Iiter-char delay
25 ms
1 set-up
TRUE
-3
Uint16
8-5* Digital/Bus
8-53
Start select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8-55
Set-up select
[3] Logic OR
All set-ups
TRUE
-
Uint8
Applications and Basic Prog...
Operating Instructions
64
Danfoss A/S © 09/2014 All rights reserved.
MG90V302
6
6