6.5 5-** Digital I/O Mode
6.5.1 5-0* Digital I/O Mode
Parameters for configuring the input and output using
NPN and PNP.
5-00 Digital I/O Mode
Option:
Function:
This parameter cannot be adjusted while the unit is
running.
Digital inputs and programmed digital outputs are
pre-programmable for operation either in PNP or NPN
systems.
[0]
*
PNP Action on positive directional pulses
(↕)
. PNP systems
are pulled down to GND.
[1]
NPN Action on negative directional pulses
(↕)
. NPN
systems are pulled up to + 24 V, internally in the
filter.
NOTICE
Once this parameter has been changed, it must be
activated by performing a power cycle.
5-01 Terminal 27 Mode
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the unit is running.
[0]
*
Input
Defines terminal 27 as a digital input.
[1]
Output Defines terminal 27 as a digital output.
5-02 Terminal 29 Mode
Option:
Function:
[0]
*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
6.5.2 5-1* Digital Inputs
Parameters for configuring the input functions for the
input terminals.
The digital inputs are used for selecting various functions
in the filter. All digital inputs can be set to the following
functions:
Digital input function
Select
Terminal
No operation
[0]
All term 32, 33
Reset
[1]
All
Stop inverse
[6]
All
Start
[8]
All term 18
Latched start
[9]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Pulse input Time Based
[32]
29, 33
Follower AF # 1 Run
Feedback
[99]
All
Follower AF # 2 Run
Feedback
[100]
All
Sleep
[101]
T18, T19, T27, T29
Table 6.8 Digital Input Functions
Functions dedicated to only one digital input are stated in
the associated parameter.
5-10 Terminal 18 Digital Input
Option:
Function:
[0]
No
operation
No reaction to signals transmitted to the
terminal.
[1]
Reset
Resets filter after a trip/alarm. Not all alarms
can be reset.
[6]
Stop inverse Stop Inverted function. Generates a stop
function when the selected terminal goes
from logical level 1 to 0.
[8]
*
Start
(Default Digital input 18): Select start for a
start/stop command. Logic 1=start, logic
0=stop.
[9]
Latched
Start
The filter starts, if a pulse is applied for
minimum 2 ms. The filter stops when stop
inverse is activated.
[23]
Set-up
select bit 0
Select Set-up select bit 0 or Select Set-up
select bit 1 to select one of the 4 set-ups.
Set
parameter 0-10 Active Set-up
to
[9] Multi
Set-up
.
[24]
Set-up
select bit 1
(Default Digital input 32): Same as
[23] Set-up
select bit 0
.
[32]
Master cmd
pulse in
Time-based pulse input measures the
duration between flanks. This gives a higher
resolution at lower frequencies, but is not as
precise at higher frequencies. This principle
has a cut-off frequency, which makes it
unsuited for encoders with very low
resolutions (e.g. 30 PPR) at low speeds.
[99]
Follower AF
#1 Run
Feedback
Do not program this setting. It is done
automatically for paralleling. See
parameter 300-40 Master Follower Selection
and
parameter 300-41 Follower ID
for more
information about paralleling.
Applications and Basic Prog...
Operating Instructions
46