Procedure
1.
In the
Security
menu (
M6
), find the Parameter lock (
P6.5.2
) with the Browser buttons.
2.
To go to the edit mode, push the Menu button Right.
3.
To change the parameter lock status, use the Browser buttons.
4.
To accept the change, push the [enter] button.
8.7.6.7 Start-up Wizard (P6.5.3)
The start-up wizard helps in the commissioning of the AC drive. By default, the start-up wizard is active.
In the start-up wizard, this information is set:
•
the language
•
the application
•
the values for a set of parameters that are same to all applications
•
the values for a set of application-specific parameters.
The table lists the functions of the keypad buttons in the start-up wizard.
Action
Button
Accepting a value
[enter] button
Scrolling for options
Browser buttons Up and Down
Changing a value
Browser buttons Up and Down
8.7.6.8 Activating/Deactivating the Start-up Wizard
Context:
Use these instructions to activate or deactivate the Start-up Wizard function.
Procedure
1.
In the
System
menu (
M6
), find the page
P6.5.3
.
2.
To go to the edit mode, push the Menu button Right.
3.
Select the action:
- To activate the start-up wizard, select
Yes
with the Browser buttons.
- To deactivate the start-up wizard, select
No
with the Browser buttons.
4.
To accept the selection, push the [enter] button.
8.7.6.9 Enabling/Disabling the Change of Multimonitoring Items
Context:
Use Multimonitoring to monitor up to 3 actual values at the same time (see
8.2 Using the Monitoring Menu (M1)
and the chapter
Monitored values in the Application Manual of your application).
Using the Control Panel
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
88 | Danfoss A/S © 2019.07