Drive type
A
B
C
D
0140 5
0062 6-0100 6
80
(3.15)
(1)
80
(3.15)
300
(11.81)
200
(7.87)
1
To change the fan with the motor cables connected, the necessary clearance on the 2 sides of the drive is 150 mm (5.91 inch).
Table 7: Necessary Quantity of Cooling Air
Drive type
Greatest possible heat loss (kW)
The quantity of cooling air [m
3
/h]
The quantity of cooling air [CFM]
0004 5-0012 5
0.2
70
41.2
0016 5-0048 5
0004 6-0034 6
1
0.75
425
250
0061 5-0105 5
0041 6-0052 6
1.9
1.2
425
250
0140 5
0062 6-0100 6
3.3
2.25
650
383
5.3 Installation Sequence for Wall-mounted AC Drives
Context:
Use these instructions to install the VACON
®
NX Wall-mounted AC Drive or VACON
®
NX Inverter FI4-FI8.
Prerequisites:
If the inverter is installed outside the enclosure, cabinet or device space, install a separate inverter cover in accordance with protection
class IP21 requirements. There is no need to install the inverter cover if the inverter is installed in an enclosure, separate cabinet, or
device space.
Mounting the Unit
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
34 | Danfoss A/S © 2019.07
Summary of Contents for VACON NX FI4
Page 1: ...Operating Guide VACON NX Inverters FI4 FI8...
Page 2: ......