vacon • 38
PROFINET IO protocol
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
0x20
Parameter text cannot be
changed
Change request to unavailable parameter text.
0x21
Invalid request ID
If a parameter request does not have the request ID
01h or 02h, this error code is returned.
0x22...0x64
Reserved (not used)
0x65
Invalid request reference
Unallowed value for request reference.
0x66
Invalid request ID
Unallowed value in request ID (neither Request Pa-
rameter nor Change Parameter).
0x67
Reserved (not used)
0x68
Invalid number of parame-
ters
Invalid number of parameters in request (0 or
greater than 39).
0x69
Invalid attribute
Invalid attribute specified in request.
0x6A
Reserved (not used)
0x6B
Request is too short
Not enough parameter value data was transmitted
in a Change request. Alternatively, the request did
not contain a complete parameter address.
0x6C
Parameter not found.
Parameter was not found or error occurred while
accessing it.
0x6D
Invalid change request.
Issue with request was found and request was not
handled.
0x6E
General error
General error occurred.
0x6F...0xFF
Reserved (not used)
Table 36. PROFIdrive parameter access errors
Error number Meaning
When used